https://www.phoenixcontact.com/us/produkte/2839211
04.10.2012Page2/7
Surge protection connector-PT 4-5DC-ST-2839211
Technical data
General
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/
Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 1.00
Width 17.7 mm
Height 45 mm
Depth 52 mm
Pitch unit 1 Div.
Protective circuit
IEC category C1
IEC category C2
IEC category C3
IEC category D1
VDE requirement class C1
VDE requirement class C2
VDE requirement class C3
VDE requirement class D1
Nominal voltage UN 5 V DC
Maximum continuous operating voltage UC 6 V DC
Maximum continuous operating voltage UC 4 V AC
Maximum continuous voltage UC (wire-wire) 6 V DC
Maximum continuous voltage UC (wire-wire) 4 V AC
Nominal current IN 2 A (80 °C)
Operating effective current IC at UC ≤ 300 µA
Ground conductor current IPE ≤ 4 µA (Directly grounded)
Ground conductor current IPE ≤ 1 µA (BE: 4+F)
Nominal discharge surge current In (8/20) µs (Core-Core) 720 A
Nominal discharge surge current In (8/20) µs (Core-Earth) 10 kA
Total surge current (8/20) µs 20 kA
Max. discharge surge current Imax (8/20) µs maximum (Core-
Core)
720 A
Max. discharge surge current Imax (8/20) µs maximum (Core-
Earth)
10 kA
Nominal pulse current Ian (10/1000) µs (Core-Core) 160 A
Lightning test current (10/350) µs, peak value limp 2.5 kA (per path)
Output voltage limitation at 1 kV/µs (Core-Core) spike ≤ 13 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 450 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 1 kV (BE: 4+F)
Output voltage limitation at 1 kV/µs (Core-Core) static ≤ 10 V
Residual voltage at In, (conductor-conductor) ≤ 40 V
Residual voltage with Ian (10/1000)µs (conductor-conductor) ≤ 20 V
Protection level UP (Core-Core) ≤ 30 V (C1 (1 kV/500 A))
Protection level UP (Core-Earth) ≤ 450 V