0902292

TMC 60 Series for mounting on 35 mm DIN rail
Overview
The TMC 60 Series provides supplemental overload and
short-circuit protection. An interrupt capacity of 10 kAIC at
480/277 V AC and dual AC/DC ratings make the series ideal
for a wide range of applications.
These DIN rail-mountable circuit breakers are available in one-,
two-, and three-pole confi gurations. An auxiliary contact in S-
or H-function status output is also available. The TMC 60 Series
is UL recognized, CSA approved and carries the CE mark.
Typical Application
Circuit protection for power supplies, UPS, controller I/O points,
relay/contactor coils, control circuits, appliances and motor circuits.
Technical Data
Circuit Breakers
Current Range 0.5 to 63 Amps
Ratings
Standard Voltage Number of Poles
UL 1077, CSA 240/415 V AC 1
415 V AC 2, 3
48 V DC 1
110 V DC 2 (in series)
Trip Characteristics C: 0.5-63A
Rated Wire Sizes - Line/Load
Rigid 35 mm² / 2 AWG min/max
Flexible 25 mm² / 3 AWG min/max
Torque 4.5 Nm / 39.8 lb
f
-in
Vibration
(per IEC 77/16.3) 3 g (in x, y, z direction)
Endurance
Electrical @ V
N,
I
N 10,000
Mechanical 20,000
Plastics Rating per UL 94 V0
Protection Level IP 20
Temperature
Operating -25˚ to +55˚C (-13˚ to +131˚F)
Storage -55˚ to +55˚C (-67˚ to +131˚F)
Configuration 1 pole 2 pole 3 pole
Weight 120 g 240 g 360 g
Thermal Magnetic Circuit Breakers - UL 1077
©2008 PHOENIX CONTACT L002487a:02.08
Dimensions
Note: all measurements in millimeters
Thermal Magnetic Circuit Breakers
Part Number Description
0902014 TMC 61C 0,5A
0902027 TMC 61C 01A
0902030 TMC 61C 02A
0902043 TMC 61C 03A
0902056 TMC 61C 04A
0902069 TMC 61C 06A
0902072 TMC 61C 10A
0902085 TMC 61C 13A
0902098 TMC 61C 16A
0902108 TMC 61C 20A
0902111 TMC 61C 25A
0902124 TMC 61C 32A
0902137 TMC 61C 40A
0902140 TMC 61C 50A
0902153 TMC 61C 63A
Part Number Description
0902166 TMC 62C 0,5A
0902179 TMC 62C 01A
0902182 TMC 62C 02A
0902195 TMC 62C 03A
0902205 TMC 62C 04A
0902218 TMC 62C 06A
0902221 TMC 62C 10A
0902234 TMC 62C 13A
0902247 TMC 62C 16A
0902250 TMC 62C 20A
0902263 TMC 62C 25A
0902276 TMC 62C 32A
0902289 TMC 62C 40A
0902292 TMC 62C 50A
0902302 TMC 62C 63A
Part Number Description
0902315 TMC 63C 0,5A
0902328 TMC 63C 01A
0902331 TMC 63C 02A
0902344 TMC 63C 03A
0902357 TMC 63C 04A
0902360 TMC 63C 06A
0902373 TMC 63C 10A
0902386 TMC 63C 13A
0902399 TMC 63C 16A
0902409 TMC 63C 20A
0902412 TMC 63C 25A
0902425 TMC 63C 32A
0902438 TMC 63C 40A
0902441 TMC 63C 50A
0902454 TMC 63C 63A
Standard current ratings and typical internal resistance values
One-pole Two-pole Three-pole
Typical time/current characteristics at 23 degrees Celsius
Direct Current - Magnetic tripping currents are increased by 30 percent in DC circuits with the effect of shifting
the magnetic trip range 30 percent to the right of Alternating Current (AC) trip curves.
10,000
1,000
100
10
1
0.1
0.01
0.001
Trip time in seconds
0.8 1 2 3 4 6 8 10 20 30 50 70 100
. . . times rated current
(multipole types: all poles symmetrically loaded)
lower trip limit 1,01 l
N
upper trip limit 1,45 l
N
rated current up to AC 6A
10,000
1,000
100
10
1
0.1
0.01
0.001
Trip time in seconds
0.8 1 2 3 4 6 8 10 20 30 50 70 100
. . . times rated current
lower trip limit 1,01 l
N
upper trip limit 1,45 l
N
rated current AC 10-40A
(50A 1-pole)
10,000
1,000
100
10
1
0.1
0.01
0.001
Trip time in seconds
0.8 1 2 3 4 6 8 10 20 30 50 70 100
. . . times rated current
lower trip limit 1,01 l
N
upper trip limit 1,45 l
N
rated current AC 63A
(50A 2+3 pol.)
The time/current characteristic curve depends on the
ambient temperature prevailing. In order to eliminate
nuisance tripping, multiply the circuit breaker current
ratings by the derating factor shown at right.
Amps Temperature ˚C
-20˚ -15˚ -10˚ -5˚ +5˚ +10˚ +15˚ +20˚ +25˚ +30˚ +35˚ +40˚ +45˚ +50˚
0.5 - 4.0 0.84 0.85 0.87 0.88 0.89 0.91 0.93 0.94 0.96 0.98 1.00 1.02 1.04 1.06 1.09
8.0 - 10 0.75 0.77 0.78 0.81 0.83 0.85 0.88 0.90 0.93 0.96
1.00 1.04 1.09 1.14 1.20
13 - 40 0.79 0.80 0.82 0.84 0.86 0.88 0.90 0.93 0.94 0.97
1.00 1.03 1.06 1.11 1.15
50-60 0.81 0.83 0.84 0.85 0.87 0.89 0.91 0.93 0.94 0.97
1.00 1.02 1.05 1.09 1.12
L002487a:02.08
© 2008 PHOENIX CONTACT
Thermal Magnetic Circuit Breakers
L002487a:02.08
PHOENIX CONTACT • P.O. Box 4100 • Harrisburg, PA 17111-0100
Phone: 800-888-7388 • 717-944-1300 • Technical Service: 800-322-3225 • Fax: 717-944-1625
E-mail: info@phoenixcon.com • Website: www.phoenixcontact.com
© 2008 PHOENIX CONTACT
Technical Data
Auxiliary Contact
Ratings Voltage 240 V AC
Current 5 A
Contacts 1 Form C
Rated Wire Sizes 2.5 mm² / 14 AWG
Weight 70 g
Contact Functions Auxiliary (H) or Signal (S)*
Accessories
* The TMC 6AUX S/H can operate as either an auxiliary contact (H function) or a
signal contact (S function). The operation of the auxiliary switch is determined at
the time of installation. The signal contact (function S) status provides the automatic
trip status of the protection device. The auxiliary (H function) provides the OPEN/
CLOSED status of the protective device. A test button on the front of the auxiliary
switch simulates functions S or H. The test button also acts as a reset for the trip
signal (function S) contacts.
Auxiliary Contact Lock Out Component
0902470 0902467
TMC 6AUX S/H TMC 6LOCKOUT
3-Phase Comb Bridge
Single Row Comb Bridge
2809241
*
2809212
*
3-Phase bridge/6 position
Single Phase/3 position
Marking
Wire End Covers
2809128
2818339 2809322
ZBN 18:UNBEDRUCKT
quantity: 10 pieces
MPB F200X16/1GS
length: 200 mm
3-Phase bridge end cover
*
Available in up to 57 positions

0902292

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Circuit Breakers TMC 62C 50A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet