2906804

https://www.phoenixcontact.com/pi/products/2906804
08/19/2018Page1/4
Surge protection device-TTC-6-1X2-24DC-PT-2906804
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection for a 2-wire floating signal circuit, e.g., 0(4) ... 20 mA current loop, HART-compatible.
Why buy this product
Space-saving installation due to the narrow overall width of 6.2 mm
Quick and tool-free installation of surge protective devices, thanks to Push-in connection technology
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4055626135588
Technical data
Dimensions
Height 105.8 mm
Width 6.2 mm +0.1 mm
Depth 69.5 mm (incl. DIN rail 7.5mm)
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Degree of protection IP20
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
https://www.phoenixcontact.com/pi/products/2906804
08/19/2018Page2/4
Surge protection device-TTC-6-1X2-24DC-PT-2906804
Technical data
General
Mounting type DIN rail: TH 35 - 7.5 mm
Type DIN rail module, one-piece
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
24 V DC
Maximum continuous voltage U
C
30 V DC
Rated current 600 mA (40 °C)
Operating effective current I
C
at U
C
≤ 5 µA
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
(8/20) µs (line-line)
5 kA
Nominal discharge current I
n
(8/20) µs (line-earth)
5 kA
Pulse discharge current I
imp
(10/350)µs (line-line)
0.5 kA
Pulse discharge current I
imp
(10/350)µs (line-earth)
0.5 kA
Total discharge current I
total
(8/20)µs
10 kA
Voltage protection level U
p
(line-line)
≤ 55 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 25 A)
≤ 55 V (C3 - 100 A)
Voltage protection level U
p
(line-earth)
≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
Voltage protection level U
p
static (line-line)
≤ 50 V (C1 - 1 kV/500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
Voltage protection level U
p
static (line-earth)
≤ 750 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
Response time t
A
(line-line)
≤ 1 ns
Response time t
A
(line-earth)
≤ 100 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm system typ. 940 kHz
Capacity (line-line) typ. 2.2 nF
Resistance in series 1.65 Ω ±20 %
Surge protection fault message none
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-line) C1 - 1 kV/500 A
https://www.phoenixcontact.com/pi/products/2906804
08/19/2018Page3/4
Surge protection device-TTC-6-1X2-24DC-PT-2906804
Technical data
Protective circuit
C2 - 10 kV/5 kA
C3 - 100 A
Impulse durability (line-earth) C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line) ≤ 700 ms
Pulse reset time (line-earth) ≤ 1500 ms
Additional technical data
Max. total discharge current I
total max
(8/20)µs
20 kA (1x)
Connection data
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Drawings
Pictogram Diagram
I [mA]
T [°C]
600
400
200
800
40 907050 60 80
Dimensional drawing
62
69,5
105,8 6,2⁺⁰¹
Circuit diagram
4
5
6
1
2
3
!
unprotected
protected

2906804

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Surge Suppressors TTC-6-1X2-24DC-PT
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet