LT4H-AC240V

17
LT4H
Setting the operation mode, time range and time
Setting procedure 1) Setting the operation mode and time range
Set the operation mode and time range with the DIP switches on the side of the LT4H timer.
DIP switches
Setting procedure 2) Setting the time
Set the set time with the keys (UP and DOWN keys) on the front of the LT4H timer.
DIP switch
Item
DIP switch No.
1 2 3
ON ON ON A: Power on delay 1
OFF OFF OFF A2: Power on delay 2
ON OFF OFF B: Signal on delay
OFF ON OFF C: Signal off delay
ON ON OFF D: Pulse One shot
OFF OFF ON E: Pulse On delay
ON OFF ON F: Signal Flicker
OFF ON ON G: Totalizing On delay
Table 1: Setting the operation mode
Table 2: Setting the time range
Operation mode
Operation mode Refer to table 1
1
2
3
Minimum input reset, start, and
stop signal width
20 ms 1 ms
*4
Time delay direction Addition
Subtraction
5
Time range Refer to table 2
6
7
8
ONOFF
DIP switch No.
6 7 8
ON ON ON 0.001 s to 9.999 s
OFF OFF OFF 0.01 s to 99.99 s
ON OFF OFF 0.1 s to 999.9 s
OFF ON OFF 1 s to 9999 s
ON ON OFF 0 min 01 s to 99 min 59 s
OFF OFF ON 0.1 min to 999.9 min
ON OFF ON 0 h 01 min to 99 h 59 min
OFF ON ON 0.1 h to 999.9 h
Time range
Notes: 1) Set the DIP switches before installing the timer.
2) When the DIP SW setting is changed, turn off the power once.
3) The DIP switches are set as ON before shipping.
ON
12345678
DIP switches
(Same for screw terminal type)
Q Elapsed time display
W Set time display
E Time delay indicator
R Controlled output indicator
T Reset indicator
Y Lock indicator
U Time units display
I UP keys
Changes the corresponding digit of
the set time in the addition direction
(upwards)
O DOWN keys
Changes the corresponding digit of
the set time in the subtraction direction
(downwards)
P RESET switch
Resets the elapsed time and the output
{ LOCK switch
Locks the operation of all keys on the unit
9
8
7
2
3
4
5
6
11
10
DOWN
UP
LOCK
RESET
sm
1
h
LOCK
RST
OP.
TIMER
LT4H
• Changing the set time
1. It is possible to change the set
time with the up and down keys even
during time delay with the timer.
However, be aware of the following
points.
1) If the set time is changed to less than
the elapsed time with the time delay set
to the addition direction, time delay will
continue until the elapsed time reaches
full scale, returns to zero, and then
reaches the new set time. If the set time
is changed to a time above the elapsed
time, the time delay will continue until the
elapsed time reaches the new set time.
2) If the time delay is set to the subtrac-
tion direction, time delay will continue
until “0” regardless of the new set time.
2. If the set time is changed to “0,” the
unit will operate differently depending
on the operation mode.
1) If the operation mode is set to A
(power on delay 1) or A2 (power on
delay 2), the output will turn on when
the power supply is turned on. However,
the output will be off while reset is being
input.
2) In the other modes, the output turns
on when the start is input. When the
operation mode is C (signal off delay),
D (Pulse one shot), or F (Signal flicker),
only when the start input is on does the
output turn on. Also, when the reset is
being input, the output is off.
Front display section
* The 8-pin type does not have the stop input, so that the dip
switch can be changed over between reset and start inputs.
The signal range of the lock input is fixed (minimum 20 ms).
• Power failure memory
The EEPROM is used for power failure memory. It has a life of Min. 10
5
over-writings.
The EEPROM is overwriting with the following timing.
* Be aware that the contents of EEPROM for all modes will be overwritten when power is turned OFF during input to external lock terminals R to E and
7
to
6
.
Such an action does not exist by doing lock operation from the front.
Output mode Overwrite timing
Power ON delay (2) A2 When power is OFF
Addition G Change of preset value or start, reset input
When power is OFF after being ON
Other modes When power is OFF after changing preset value
Digital
Timers
09/2009
18
LT4H
Operation mode
T: Set time t1, t2, t3, ta<T
Operation type
Power on delay (1)
Explanation Time chart
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Clears elapsed time value and starts time
delay at power ON.
After timer completion, stops at the display of
the set value (addition), or stops at “0” (sub-
traction).
• Ignores start input.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
A
Power on delay (2)
A2
Signal on delay
B
Signal off delay
C
Stop
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Tt1
t2
t1+t2=T
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Tt1t2
t1+t2=T
Stop
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T
t1
t2 t1+t2=T
Stop
Start
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T
ta tb t
T>ta+tb T>t
Stop
Start
Reset
Output
Power supply
123
ON ON ON
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Elapsed time value does not clear at power
ON. (power outage countermeasure function)
The output remains ON even after the power
is cut and restarted.
After timer completion, stops at the display of
the set value (addition), or stops at “0” (sub-
traction).
• Ignores start input.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
123
OFF OFF OFF
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
Time delay starts at start ON and elapsed
time value or output resets at start OFF.
Instantaneous time delay start at reset OFF
and power ON while start is ON.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
ON OFF OFF
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
Output control ON at start ON and time delay
start at start OFF.
Elapsed time value clears when start goes ON
again during time delay.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
123
OFF ON OFF
Notes: 1) Each signal input (start, reset, stop, and lock) is applied by shorting their input terminal to the common terminal (terminal Q for the 8-pin type, terminal E for
the 11-pin type, and terminal for the screw terminal type).
2) The 8-pin type does not have a stop input or lock input.
Digital
Timers
09/2009
19
LT4H
Operation type
Pulse One-shot
Explanation Time chart
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
Time delay starts and output control ON at
start ON.
Turns output control OFF and clears elapsed
time value at time-up.
• Ignores start input during time delay.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
D
Pulse On delay
E
Signal Flicker
F
Totalizing On delay
G
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T T
t1
t2
ta
T=t1+t2
T>ta
t
Stop
Start
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Tt2
T=t1+t2
T Tt1
Stop
Start
Reset
Output
Power supply
T>ta
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
t1 t1
T=t1+t2
T=t1+t2
tat2
t2
T
T T
Stop
Start
Reset
Output
Power supply
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
T
t1
t2 t3 ta
T=t1+t2+t3
T>ta
Stop
Start
Reset
Output
Power supply
123
ON ON OFF
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
• Time delay starts at start ON.
• Ignores start input during time delay.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
OFF OFF ON
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
• Clears elapsed time value at power ON.
• Time delay starts at start ON.
• Ignores start input during time delay.
Output control reverses, elapsed time value
clears, and timer delay starts at timer comple-
tion.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
In order to have the time delay start at power
ON or reset at power OFF, short out the start
input beforehand.
123
ON OFF ON
Set the operation mode
section of the DIP switches
(no.’s 1, 2, and 3) on the
side of the timer as shown.
Elapsed time value does not clear at power
ON. (power outage countermeasure function)
The output remains ON even after the power
is off and restarted.
Stops delay time operation at stop ON.
Restarts delay time operation at stop OFF.
123
OFF ON ON
Notes: 1) Each signal input (start, reset, stop, and lock) is applied by shorting their input terminal to the common terminal (terminal Q for the 8-pin type, terminal E for
the 11-pin type, and ter- minal
6
for the screw terminal type).
2) The 8-pin type does not have a stop input or lock input.
6
Digital
Timers
09/2009

LT4H-AC240V

Mfr. #:
Manufacturer:
Panasonic Industrial Devices
Description:
Timers 240VAC SCREW
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet