Toroidal L.V. - Chassis Mount
182 Series
Note: This product line will soon be discontinued as a stocked series. Available while quantities last. It has
been replaced with 1182 Series. For alternative solution assistance, please contact Hammond Customer
Service - sales@hammfg.com or USA (716) 630-7030, Canada and International (519) 822-2960.
Features
Low profile, lightweight, cool running - due to high efficiency toroidal
design
Dual 117/234 VAC primary, 50/60 Hz. operation
Units are designed to have all windings engaged.
Center single hole mounting - units over 225VA include a potted center (see
photos below) for extra mounting strength.
Supplied with two rubber insulating pads, one metal centering washer and
all mounting hardware (160VA and under)
Supplied with one bottom rubber insulating pad and mounting hardware
(225VA and larger)
Center bolt size varies with VA - see tables below.
Minimum 8" long flexible leads
Hi-Pot test of 4,000V RMS between primary & secondary
CSA certified to C22.2 #66 - CSA file #209651
UL recognized to UL506 - UL file #E207860
CE certified to IEC950
Note about Inrush Current:
Due to the superior magnetic properties of Toroidal transformers they will
be susceptible to high magnetizing current when initially energized, only
limited by the low DC resistance of the primary winding. Depending on
where you are in the AC cycle when the transformer is energized dictates
the chances of overloading the supply circuit. This is why the transformer
may sometimes energize without a problem and other times it will blow the
fuse or trip the circuit breaker. The duration of this overload is rarely longer
than a half of a cycle. Therefore, you should consider using a slow-blow
fuse, time delayed circuit breaker or other form of soft start circuitry for the
supply line when using these high efficient Toroidal transformers.
Quality Products. Service Excellence.