D1U-H-2800-52-HBxC Series
AC/DC Front End Power Supply
D1U-H-2800-52-HBxC.B01 Page 1 of 5
www.murata-ps.com
www.murata-ps.com/support
For full details go to
www.murata-ps.com/rohs
SELECTION GUIDE
Part Number
Power Output
High Line AC
Main
Output
Standby
Output
Airflow Current Share
D1U-H-2800-52-HB1C 2800W -52V 12V Front to back Active
D1U-H-2800-52-HB1DC 2800W -52V 12V Front to back Droop
INPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Input Voltage Operating Range 170 230 264 Vac
Input Frequency 47 55 63 Hz
Turn-on Input Voltage Ramp up 160 170
Vac
Turn-off Input Voltage Ramp down 155 165
Maximum Rated Input Current 200VAC 16 Arms
Inrush Current Cold start 50 Apk
Inrush Current Cold start between 0-1msec 100 Apk
Power Factor
Output load >90% 95%
Output load >50% 75%
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter Conditions Min. Typ. Max. Units
-52V
Voltage Set Point Accuracy -52
Vdc
Line and Load Regulation 51.48 52.52
Ripple Voltage & Noise 20MHz Bandwidth 520 mV p-p
Output Current 1 54 A
Load Capacitance 6800 µF
12Vsb
Voltage Set Point Accuracy 12
Vdc
Line and Load Regulation 11.2 12.4
Ripple Voltage & Noise 120 mV p-p
Operating Range 0 0.5 A
Load Capacitance 1000 µF
FEATURES
nRoHS compliant
n2800W (220Vac) Output Power
n-52V Main output, 12V standby output
n1U sized; dimensions 5.5"x11.4"x1.61"
n27.7 Watts per cubic inch density
nN+1 redundancy capable,
including hot-docking
nActive current sharing or droop current
sharing
nOver-voltage, over-current,
over-temperature protection
nInternal cooling fans
nI²C Bus interface with status indicators
nOptional 1U x 19" power-shelf
PRODUCT OVERVIEW
The D1U-H-2800 is a 2800 Watt, power-factor-corrected (PFC) front-end power supply for hot-swapping
redundant systems. The main output is -52V and standby output of 12V. Packaged in 1U low profile, it is
designed to deliver reliable bulk power to telecom systems or any -52V distributed power architecture
systems requiring high power density. The highly efficient electrical and thermal design with internal
cooling fans supports reliable operation conditions. The D1U-H-2800 is designed to auto-recover from
over-current and over-temperature faults. Status information is provided with front panel LEDs, logic
signals and I
2
C management interface. Three units can be packaged into an optional 19" 1U power shelf
to provide up to 8.4kW of power.
1
Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of
the power supply outputs. The output noise requirements apply over a 0 Hz to 20 MHz bandwidth. A short coaxial
cable with 50ohm scope termination is used.
To Be Discontinued*
*LAST TIME BUY: 10/1/2017. CLICK HERE FOR DISCONTINUANCE NOTICES.