https://www.phoenixcontact.com/us/products/2982757
04/27/2016Page2/6
Reversing load relay-ELR W1/ 6-24DC/RDT-2982757
Technical data
Input data
Surge protection
Surge voltage protection > 33 V DC
Typical response time 200 µs
Status display LED yellow, forward running (R), LED yellow, reverse running (L)
Current consumption 3 mA
Switchover time R
L
/L
L
(turn-on time)
1 ms
Output data load output
Nominal output voltage range 10 V DC ... 30 V DC
Protective circuit Reverse polarity protection
Connection data, control circuit
Connection name Control circuits
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 6 mm²
Conductor cross section flexible 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 10
Connection data load circuit
Connection name Load circuit
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 6 mm²
Conductor cross section flexible 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 10
General
Test voltage input/output 2.5 kV AC
Mounting position Vertical (horizontal DIN rail)
Assembly instructions Any
Operating mode 100% operating factor
Designation Air clearances and creepage distances between the power circuits
Standards/regulations EN 50178
Insulation Basic insulation
Degree of pollution 2
Overvoltage category III