PLC-RPIT- 24UC/21AU Order No.: 2900307
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900307
PHOENIX CONTACT Inc., USA Page 2 / 6
http://www.phoenixcon.com Aug 24, 2011
Typical response time 6 ms
Typical release time 15 ms
Operating voltage display Yellow LED
Protective circuit Bridge rectifier Bridge rectifier
Contact side
Contact type Single contact, 1-PDT
Contact material AgSnO, hard gold-plated
Maximum switching voltage 30 V AC
36 V DC
Minimum switching voltage 100 mV (at 10 mA)
Maximum inrush current 50 mA
Min. switching current 1 mA (at 24 V)
Limiting continuous current 50 mA
Interrupting rating (ohmic load) max. 1.2 W (at 24 V DC)
Note the following values are applicable if a gold layer is
destroyed
Maximum switching voltage 250 V AC/DC
Minimum switching voltage 5 V (at 100 mA)
Limiting continuous current 6 A
Min. switching current 10 mA (at 12 V)
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W (for 48 V DC)
18 W (for 60 V DC)
23 W (for 110 V DC)
40 W (for 220 V DC)
1500 VA (for 250 V AC)
General data
Width 6.2 mm
Height 80 mm
Depth 94 mm
Test voltage relay winding/relay contact 4 kV AC (50 Hz, 1 min.)
Ambient temperature (operation) -40 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Operating mode 100% operating factor
Mechanical service life
2 x 10
7
cycles