125
E-RATED MEDIUM VOLTAGE
15.5 kV FUSES
CROSS REFERENCE
NEW EDISON OLD EDISON BUSSMANN GOULD (old/new) WESTINGHOUSE GE (old/new)
MV155F1CBX — JCN (15-25)E A1550X – 1B/A155F1CORO — —
MV155F1DBX 15.5FFVHA JDN (15-100)E A1550X – 1F/A155F1DORO (10-50E) 15HLE–xxxE 9F60FMH/9F62DDD
MV155F2DBX 15.5FFVHK — — — —
MV155F1DCX — JCN (30-100)E A1550X – 1D/A155F1DORO (65-100E) — —
MV155F2DCX — — A1550X – 1D/A155F2DORO (125-200E) — —
“E”-Rated Power Fuses Having Full Range Clearing Capability for Medium Voltage
Transformer Circuit Protection.
Part Current Length Dia. # of Clip
Number Rating (In) (In) Barrels Center (In)
MV155F1CBX5E 5E 18.75 2 1 15
MV155F1CBX7E 7E 18.75 2 1 15
MV155F1CBX10E 10E 18.75 2 1 15
MV155F1CBX15E 15E 18.75 2 1 15
MV155F1CBX20E 20E 18.75 2 1 15
MV155F1CBX25E 25E 18.75 2 1 15
MV155F1CBX30E 30E 18.75 2 1 15
MV155F1DBX10E 10E 18.75 3 1 15
MV155F1DBX15E 15E 18.75 3 1 15
MV155F1DBX20E 20E 18.75 3 1 15
MV155F1DBX25E 25E 18.75 3 1 15
MV155F1DBX30E 30E 18.75 3 1 15
MV155F1DBX40E 40E 18.75 3 1 15
MV155F1DBX50E 50E 18.75 3 1 15
MV155F1DBX65E 65E 18.75 3 1 15
MV155F1DBX80E 80E 18.75 3 1 15
MV155F1DBX100E 100E 18.75 3 1 15
MV155F2DBX125E 125E 18.75 3 2 15
MV155F2DBX150E 150E 18.75 3 2 15
MV155F2DBX175E 175E 18.75 3 2 15
MV155F2DBX200E 200E 18.75 3 2 15
MV155F1DCX65E 65E 21.75 3 1 18
MV155F1DCX80E 80E 21.75 3 1 18
MV155F1DCX100E 100E 21.75 3 1 18
MV155F2DCX125E 125E 21.75 3 2 18
MV155F2DCX150E 150E 21.75 3 2 18
MV155F2DCX175E 175E 21.75 3 2 18
MV155F2DCX200E 200E 21.75 3 2 18
MV155 SPECIFICATIONS
E-RATED MEDIUM VOLTAGE FUSES
Meets E-Rating requirements of ANSI C37.46
Meets Full Range requirements of ANSI C37.40.
Voltage Rating: 15,500 Volts AC
Interrupting Rating: 50kA Maximum Symmetrical Amps
Current Limiting
Agency Approvals:
UL Pending
Part Number Construction
Medium Voltage # of Barrel Clip Center Indication Ampere
Voltage Rating Barrels Diameter Distance Type Rating
Example MV 155 F 1 C B X 5E
055 = 5.5KV F = Full Range 1 C = 2 in. A = 12 in. X = Indicator
155 = 15.5KV 2 D = 3 in. B = 15 in. H = Striker Pin
C = 18 in.
BENEFITS:
• Standard clip center lengths and barrel diameters.
• Standard blown fuse indication. For heavy striker pin
replace “X” in part number with “H”.
• 100% tested for reliability.
• Suitable for indoor or outdoor usage.
• Full Range capability.
APPLICATIONS:
• For transformer and feeder protection.
RECOMMENDED FUSECLIPS:
Refer to page 16 in this catalog.