SLR2.100

slr2e100 / 040121 1/2
Data sheet
The
Redundant
Variant
Baby with redundancy
SLR2.5
Input: AC 230V/115V, DC 160-375V
Output: 24V/2.5A
High overload current, no switch-off
Quasi-Wide-Range Input
N+1 redundancy, RDY relay contact
NEC Class 2 Power Supply
CUL/CSA-C22.2
EMC and
Low Volt.
UL60950 E137006
UL508 LISTED
IND. CONT. EQ.
No 950-M90
18 WM, 60°C
Directive
CB
scheme
IEC60950
Input
Efficiency, Reliability etc.*
Construction / Mechanics*
Output
* *For further information see data sheets „The SilverLine“, „SilverLine Family
Branches“ and mechanics data sheet
Input voltage AC100-120/220-240 V (switchable), 47-63 Hz
(85-132 VAC / 176-264 VAC, 160-375 VDC, see
also „Output: Continuous Loading“)
Quasi-Wide-Range Input: With the switch in the 230V position the pow-
er-supply unit operates at low and moderate loads at any input voltage
between 95 and 264 V AC (see ’Output’ at the right side).
Note: At DC input, always leave the switch in the 230V position
Input current < 1.3 A (switch in 115V position)
< 0.7 A (switch in 230V position)
DC input current
at open output
typ. 5.3 mA at 110 VDC, 3.9 mA at 300 VDC
(preserves battery sources)
Inrush current typ. < 25 A at 264 V AC and cold start
To be fused with a 10A, B-type 'circuit-breaker' switch based on the
usual thermomagn. overload sensing principle (used anyway to fuse
the input lines). In addition, the unit contains an internal fuse (not ac-
cessible)
Transient
handling
Transient resistance acc. to VDE 0160 / W2
(750 V / 1.3 ms), for all load conditions.
Hold up time > 20 ms at 196 VAC, 24 V / 2.5 A
(see diagram overleaf)
Efficiency typ. 86.5 % (230 VAC, 24 V / 2.5 A)
Losses typ. 9.4 W (230 VAC, 24 V / 2.5 A)
MTBF 700,000 h acc. to Siemensnorm SN 29500
(24 V/2.5 A, 230 VAC, T
amb
= +40 °C)
Life cycle (electrolytics) The unit exclusively uses longlife electrolytics,
specified for +105°C (cf. ’The SilverLine’, p.2).
Housing dimensions and Weight
W x H x D
Free space for
ventilation
•Weight
49 mm x 124 mm x 102 mm (+ DIN rail)
above/below 25 mm recommended
right 10 mm recommended (front view)
470 g
Design advantages:
Input and output pluggable by means of Combicon® plug connec-
tor.
Ensure strain relief of the plug connectors
when installing the unit.
Input and output are strictly apart from each other and so cannot be
mixed up (input below, output above).
Rated output voltage 24 V DC
For balanced current sharing during parallel operation:
Soft characteristic (25.2 V DC ±2% at no-load, 24 V DC ±0.5% at nomi-
nal load, almost linear characteristic curve)
Output noise
suppression
Radiated EMI values below EN 61000-6-3, even
when using long, unscreened output cables.
Ambient temperature
range T
amb
Operation: -10°C...+70°C (>60°C: Derating)
Storage: -25°C...+85°C
Output protected against short circuit, open circuit and overload
Derating typ. 1.5 W/K (at T
amb
=+60°C...+70°C)
Voltage regulation better than 2% Vout overall
Ripple / Noise < 30 mV
PP
, (20 MHz bandw., 50 measurem.)
Overvolt. protection typ. 32 V
Parallel operation yes; current sharing via soft characteristic
(see diagram)
Power back immunity 26 V
Front panel indicator Green LED
RDY relay contact
•Type
•closes
opens
Electrical isolation
Contact rating
normally open contact
when output voltage > 22.1V ±4%
when output voltage < 19.8V ±4%
500V DC to output voltage
1A at 28V DC
Continuous loading
(at T
amb
= -10°C...+60°C,
convection cooling),
see also diagram over-
leaf. For start at
T
amb
<0°C and low input
voltage, please contact
PULS.
* For start with DC input
> 95 V DC needed
Switch AC/DCin Iout
230V 176-264 V ACin 2,5 A
95-176 V ACin 1,5 A
160-375 V DCin 2,5 A
120-160 V DCin 2,0 A
80*-120 V DCin 1,5 A
Order information
Order number Description
SLR2.100
SL2.100
SLZ01
N+1 redundancy*
Basic version without redundancy*
Screw mounting set, two needed per unit
Your partner in power supply:
European
Power Supply
Manufacturers
Association
PULS GmbH
Arabellastraße 15
D-81925 München
Tel.: +49 89 9278-0
www.puls-power.com
Fax: +49 89 9278-199
Data sheet
2/2 slr2e100 / 040121
Bayerns Best 50
Czech 100 Best
EuropeÕs 500
Unless otherwise stated, specifications are valid for AC 230V input voltage, +25°C ambient temperature, and 5 min. run-in time. They are subject to change without prior notice.
Start / Overload Behaviour
Further information
Start-up delay typ. 0.1 s
Rise time ca. 5-20 ms, depending on load
Overload Behaviour
Special PULS Over-
load Design (see
right diagram)
no disconnection, no hiccup if overloaded
high overload current (up to 1.5 I
Nom
), Vout
is gradually reduced with increasing cur-
rent.
Advantages:
High short-circuit current, giving large ’start-up window’: unit starts
reliably even with awkward loads (DC-DC converters, motors).
No ’sticking’ such as can occur with fold-back characteristics
Secondary fuses operate reliably
Further information, especially about
•EMC
Connections
Safety, Approvals
Mechanics and Mounting
see page 2 of „The SilverLine“ data sheet.
For detailed dimensions
see SilverLine mechanics data sheet SLR2.5/ 5/ 10
Power wiring
SLR2.5
GND +24V
N
+
L
SLR2.5
N
+
L
0
4
8
12
16
20
24
28
0123456
Output current Iout [A]
Output voltage Vout [V]
Tamb = 60°C / 4C / 2C / 0 °C
0
10
20
30
40
50
60
70
80
90
100
90 120 150 180 210 240
Inp ut voltage VACin [V]
Hold-up time [ms]
Iout=1,5
A
Iout=2,5
A
Iout=1,0
A
Iout=1,5
A
Iout=2,5
A
Switch pos .
115V
Switch pos
230V
ACin
0
10
20
30
40
50
60
70
80
90
100
80 120 160 200 240 280 320
Input voltage VDCin [V]
Hold-up time [ms]
Iout=2,5
Iout=1,5
Iout=1,0
DCin
Output Current over Input Voltage (min.)
Hold-up time (min.)
Output characteristic (min.)
1
2
Input voltage VACin [V]
Output current Iout [A]
3
1
2
3
100 200 300 400
100 200 300 400
Input voltage VDCin [V]
switch at 115V
80 375160
85
95
132 264
ACin
DCin
>95 VDC für Start
176
switch at 230V

SLR2.100

Mfr. #:
Manufacturer:
Description:
DIN RAIL REDUN PSU 60W 24V 2.5A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet