IB IL 24 DI 32/HD-PAC Order No.: 2862835
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2862835
PHOENIX CONTACT Deutschland GmbH Page 2 / 6
http://www.phoenixcontact.de Feb 8, 2011
Note on dimensions Housing dimensions
Weight 185 g
Note on weight specifications with male connectors
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 5 V supply incoming remote bus/7.5 V supply (bus logic) 500 V
AC 50 Hz 1 min
5 V supply outgoing remote bus/7.5 V supply (bus logic) 500 V
AC 50 Hz 1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Diagnostics messages No None
Interface
Fieldbus system Lokalbus
Name Inline local bus
Type of connection Inline data jumper
Transmission speed 500 kbps
Power supply for module electronics
Connection method Via potential routing
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Ripple 5%
Supply current max. 90 mA
Derating No derating
Communications power U
L
7.5 V (via voltage jumper)
Current consumption max. 90 mA (from the local bus)
Power consumption max. 0.675 W (at U
L
)