PSI-MODEM-SHDSL/SERIAL
104460_en_04 PHOENIX CONTACT 5/9
RS-422 interface
Connection method Plug-in/screw connection via COMBICON plug
Type RS-422 interface, according to ITU-T V.11, EIA/TIA-422,
DIN 66348-1
Transmission rate Can be freely parameterized from 92 bps ... 2 Mbps
Transmission length Maximum 1200 m
Supported protocols Modbus RTU/ASCII and others, transparent protocol
Data format/coding Serial asynchronous UART/NRZ, 7/8 data bits, 1/2 stop bits,
1 parity bit (even, odd, mark, space, none),
9/10/11-bit character length
RS-485 interface
Connection method Plug-in/screw connection via COMBICON plug
Type RS-485 interface, according to EIA/TIA-485, DIN 66259-
4/RS-485 2-wire
Transmission rate Can be freely parameterized from 92 bps ... 2 Mbps
Transmission length Maximum 1200 m
Supported protocols Modbus RTU/ASCII and others, transparent protocol
Data format/coding Serial asynchronous UART/NRZ, 7/8 data bits, 1/2 stop bits,
1 parity bit (even, odd, mark, space, none),
9/10/11-bit character length
USB interface (configuration/diagnostics)
Connection method Mini-USB type B, 5-pos.
Type USB 2.0
Transmission length Maximum 5 m, only for configuration and diagnostics
General data
Ambient temperature range
Operation (no other modules supplied via the device):
– Freestanding (40 mm spacing)
– Connected in series (low power dissipation of mod-
ules connected in series)
– Connected in series (without restrictions)
-20°C ... +60°C
-20°C ... +55°C
-20 °C ... +50 °C
Operation (other modules supplied via the device (max.
1.5 A))
-20 °C ... +45 °C
Storage/transport -40 °C ... +85 °C
Housing ME 35 with 5-pos. bus contact and ground contact
Material PA 6.6-FR, V0, green
Dimensions (H x W x D) 99 x 35 x 114.5 mm
Weight 205 g
Functional earth ground Housing contact to DIN rail
Degree of protection IP20
Electrical isolation DIN EN 50178
(Supply // RS-485, RS-422 // DSL port A // DSL port B // FE)