BATTERY
Full Load Runtime (min.) 4.9 min. (1350w)
Half Load Runtime (min.) 14 min. (675w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility <a class="productLink" href="//www.tripplite.com/External-36V-2U-Rack-Tower-Battery-Pack-for-select-Tripp-
Lite-UPS-Systems-BP36V15-2U~BP36V15-2U">BP36V15-2U</a> (limit 1); <a class="productLink"
href="//www.tripplite.com/External-36V-3U-Rack-Tower-Battery-Pack-select-Tripp-Lite-UPS-Systems-BP36V42-
3U~BP36V42-3U">BP36V42-3U</a> (multi-pack compatible); <a class="productLink"
href="//www.tripplite.com/external-36v-2u-rack-tower-battery-pack-select-tripp-lite-ups-systems~BP36V27-
2US">BP36V27-2US</a> (multi-pack compatible)
DC System Voltage (VDC) 36
Battery Recharge Rate (Included
Batteries)
Less than 4.5 hours from 10% to 90%
Internal UPS Replacement Battery
Cartridge
<a class="productLink" href="//www.tripplite.com/2U-UPS-Replacement-36VDC-Battery-Cartridge-1-set-3-
select-Tripp-Lite-SmartPro-UPS~RBC93-2U">RBC93-2U</a>
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage Correction Input voltages between 127 and 145 are reduced by 12%
Undervoltage Correction Input voltages between 95 and 108 are boosted by 12%
Severe Undervoltage Correction Input voltages between 83 and 94 are boosted by 24%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for
detailed LCD configuration and monitoring options)
Switches 3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions
Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 570
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
4 / 6