2
NE1A-SCPU Series
Safety Input Specifications
Safety Output Specifications
Test Output Specifications
*The maximum current for simultaneously ON outputs is 1.4 A.
(T0 to T3: NE1A-SCPU01-V1, T0 to T7: NE1A-SCPU02)
A 15 to 400-mA, 24-VDC external indicator can be connected to T3
and T7.
DeviceNet Communications Specifications
Input type Sinking inputs (PNP)
ON voltage
11 VDC min. between each terminal and
ground
OFF voltage
5 VDC min. between each terminal and
ground
OFF current 1 mA max.
Input current 4.5 mA
Output type Sourcing outputs (PNP)
Rated output
current
0.5 A max./output
ON residual
voltage
1.2 V max. between each output terminal and
V2
Leakage current 0.1 mA max.
Output type Sourcing outputs (PNP)
Rated output
current
0.7 A max./output *
ON residual
voltage
1.2 V max. between each output terminal and
V1
Leakage current 0.1 mA max.
Communications protocol DeviceNet compliant
Connection form Multi-drop system and T-branch system can be combined (for trunk line and branch lines)
Communications speed 500/250/125 kbps
Communications media Special cable, 5 conductors (2 for communications, 2 for power supply, 1 for shielding)
Communications distance
Communications power supply 11 to 25 VDC
No. of connectable nodes 63
Safety I/O communications
(Pre-Ver. 1.0)
Safety Master function
• Max. no. of connections: 16
• Max. data size: Input 16 bytes or output 16 bytes (per connection)
• Connection type: Single-cast, multi-cast
Safety Slave function
• Max. no. of connections: 4
• Max. data size: Input 16 bytes or output 16 bytes (per connection)
• Connection type: Single-cast, multi-cast
Safety I/O communications
(unit version 1.0 or later)
Safety Master function
• Max. no. of connections: 32
• Max. data size: Input 16 bytes or output 16 bytes (per connection)
• Connection type: Single-cast, multi-cast
Safety Slave function
• Max. no. of connections: 4
• Max. data size: Input 16 bytes or output 16 bytes (per connection)
• Connection type: Single-cast, multi-cast
Standard I/O communications
(all unit versions)
Standard Slave function
• Max. no. of connections: 2
• Max. data size: Input 16 bytes or output 16 bytes (per connection)
• Connection type: Poll, bit-strobe, COS, cyclic
Message communications Max. message length: 552 bytes
Note: Figures in parentheses ( ) indicate values when a thin cable is used.
Communications speed Max. network length Branch length Total branch length
500 kbps 100 m max. (100 m max.)
6 m max.
39 m max.
250 kbps 250 m max. (100 m max.) 78 m max.
125 kbps 500 m max. (100 m max.) 156 m max.