https://www.phoenixcontact.com/us/products/2942823
10/31/2014Page2/4
Solid-state relay module-EMG 17-OV-230AC/ 48DC/2-2942823
Technical data
Input data
Nominal input voltage U
N
230 V AC
Input voltage range in reference to U
N
0.8 ... 1.1
Switching threshold "0" signal, voltage ≤ 155 V AC
Switching threshold "1" signal voltage ≥ 180 V AC
Typical input current at U
N
9 mA
Typical response time
25 ms (at U
N
= 24 V AC)
Typical turn-off time
35 ms (at U
N
= 24 V AC)
Status display Yellow LED
Type of protection Protection against polarity reversal
Protective circuit/component Polarity protection diode
Transmission frequency 3 Hz
Output data
Output nominal voltage 48 V DC
Output voltage range 12 V DC ... 48 V DC
Limiting continuous current 2 A (see derating curve)
Maximum inrush current 5 A (t = 1 s)
Peak offstate voltage 60 V DC (Collector-emitter reverse voltage)
Voltage drop at max. limiting continuous current 1.1 V
Output circuit 3-conductor, ground-referenced
Type of protection Protection against polarity reversal
Surge protection
Protective circuit/component Polarity protection diode
Suppressor diode
Connection data
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 12
General
Test voltage input/output 3.5 kV AC
3.5 kV AC