Surge arrester B88069X4390B152
2-electrode arrester V13-A500X
PPD AB PD / PPD AB PM Version: 07 / 2018-04-10
Please read Cautions and warnings and Page 2 of 5
Important notes at the end of this document.
Features Applications
Suitable for direct strikes
Very fast response time
Stable performance over life
High insulation resistance
RoHS-compatible
AC power line N-PE application
Class II – surge protection
Electrical specifications
DC spark-over voltage
1) 2)
400 … 600 V
Front of wave spark-over voltage
- at 1.2/50 µs, 6 kV < 1500 V
Breakdown time
- typical values
< 100
< 20
ns
ns
Insulation resistance at 100 V
DC
> 1
GΩ
Class II according to IEC 61643-11
Max. continuous operating voltage at 50/60 Hz U
c
Nominal discharge current 8/20 µs I
n
Maximum discharge current 8/20 µs I
max
Follow current at 50/60 Hz I
f
255
20
40
100
V
kA
kA
A
AC discharge current (TOV
3)
at 1200 V)
1 operation 50 Hz, 0.2 s 300 A
Weight ~ 8 g
Operation and storage temperature -40 ... +90 °C
Climatic category (IEC 60068-1)
40/090/21
Marking, black positive
500 YY O
500 - Nominal voltage
YY - Year of production
O - Non radioactive
Certification UL 497B (E163070)
1)
At delivery AQL 0.65 level II, DIN ISO 2859
2)
In darkness without storage
3)
TOV – Temporary over voltage