GPFC250-12G

GPFC250 Commercial/GPFM250 Medical
250 Watt Global Performance Switchers
• 3.6 watts/cu.in. power density
• Compact size (5.0” x 8.0” x 1.75”)
• Power factor corrected to IEC 1000-3-2, Class A
• Less than 300 μA leakage
• Conducted EMI exceeds FCC Class B and CISPR 22 Class B
(Commercial models) and CISPR 11 Class B (Medical models)
• Commercial Approved to UL1950, IEC950, EN60950 and
CSA 22.2 No. 950
• Medical Approved to UL2601-1, IEC601-1/60601-1 and
CSA-C22.2 No. 601.1
• 2-year warranty
• RoHS Compliant Model Available (G sux)
GLOBAL PERFORMANCE SWITCHERS
FEATURES:
EMI SPECIFICATIONS COMPLIANCE LEVEL
Conducted Emissions GPFC250
Conducted Emissions GPFM250
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
EN55022 Class B; FCC Class B
EN55011 Class B: FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
EN61000-4-5, 1 kV di., 2 kV com.
Ac Input
85-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current 3.7 A at 90 Vac, 60 Hz with full rated load. Input cur-
rent harmonic content meets the requirements of IEC1000-3-2 Class A for all
load conditions.
Hold-upTime
25 ms minimum from loss of ac input at full load, nominal line (115 Vac).
Minimum Load: No minimum load required
Output Power
250 W fan cooled, 180 W convection. See chart for models under 12 V.
Overload Protection
Fully protected against short circuit and output overload. Short circuit protec-
tion is cycling type power limit or foldback type depending on model and
output. Recovery after fault is automatic. Individual output current limits are
a function of load distribution and degree of overload.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz Bandwidth, dierential mode. Measured with
noise probe directly across output terminals of the power supply.
Transient Response
Main Output–500 μs typical response time for return to within 0.5% of nal
value for a 50% load step change, Di/Dt< 0.2 A/μs. Maximum voltage devia-
tion is 3.5%.
Remote Sense
Provided as a standard feature. Capable of compensating for 0.25 V total of
cabling losses in voltage.
Overvoltage Protection
Built in on all models. Output voltage decay is dependent upon loading.
Voltage Adjustment
Main output ±5%.
Ecency
Minimum 80% on 12-48 V units, 75% on 5 & 3.3 V units at full rated load.
Input Protection
Internal ac fuses provided on all models. Fuses do not blow on overload or
short circuit—fuses blow only if catastrophic failure occurs in the unit.
EMI/EMC Compliance
All models include built-in EMI ltering to meet emissions requirements:
Inrush Current
Inrush 240 Vac is less than 37 A, averaged over the rst ac half-cycle under cold
start conditions. Limiting provided by internal thermistors.
Fan Output
An additional 12 Vdc, 250 mA output suitable for powering a dc fan is included in
all models.
Thermal Shutdown
Provided as a standard feature. Designed to protect unit from prolonged over
temperature.
Power Fail
TTL or CMOS compatible output goes low (<0.5 V) 8 ms before output voltage
drops more than 4% below nominal voltage upon loss of ac power. The signal is
factory set to trip when input power can no longer sustain the output.
Temperature Coecient
0.03% / °C typical on all outputs.
Leakage Current
70μA under normal conditions (132 Vac @ 60 Hz).
Maximum under single fault conditions (264 Vac @ 60Hz), 250 μA.
Power Good
TTL/CMOS compatible output goes high more than 100 ms after V1 reaches the
under voltage threshold and should assure that sucient energy is stored in the
input
section to provide normal power fail/shutdown. The signal will fall to a low state
(<0.5 V) when V1 goes below 95% of the rated voltage.
External O
TTL/CMOS compatible input shuts down power converter. A logic high (>2.7 V
with 400 uA source) shuts down the power converter. A logic low (<0.5 V) or an
open circuit allows the supply to run. 3.3 V & 5 V models require 25 mA source.
SPECIFICATIONS
All specications are typical at nominal input, full load at 25
O
C unless otherwise stated
SL Power Electronics Corp., 6050 King Drive, Bldg. A, Ventura, CA, 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 Email: info@slpower.com Rev. 4/9/07.
Data Sheet © 2006 SL Power Electronics Inc. The information and specications contained in this data sheet are believed to be correct at time of publication.
However, SL Power accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specications are subject to change without notice.
ENVIRONMENTAL SPECIFICATIONS OPERATING NON-OPERATING
Temperature (A) 0 to 5 -40 to +85°C
Humidity (A) 0 to 95% RH 0 to 95% RH
Shock (B) 20 g
pk
40 g
pk
Altitude -500 to 10,000 ft -500 to 40,000 ft
Vibration (C) 1.5 g
rms’
0.003 g
2
/Hz
5 g
rms’
0.026 g
2
/Hz
GPFC250/GPFM250 MECHANICAL SPECIFICATIONS
A. Units should be allowed to warm up/operate under non-condensing
conditions before application of power. Derate output current and total
output power by 2.5% per °C above 50°C.
B. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction, 3
orthogonal axes, total 6 shocks.
C. Random vibration—10 to 2000Hz, 6dB/octave roll-o from 350 to
2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating and 1
hr./axis non-operating.
INPUT:
TB1
6-32, 3 PIN TERMINAL BLOCK 0.375”
PIN 1) AC LINE
PIN 2) AC NEUTRAL
PIN 3) AC GROUND
SIGNALS: J2
AMP P.C.B. HEADER P/N 640456-5
MATING CONNECTOR P/N640440-5
PIN 1) DC GOOD
PIN 2) POWER FAIL
PIN 3) EXT OFF
PIN 4) +SENSE
PIN 5) -SENSE
FAN
AMP P.C.B. HEADER P/N 640456-2
MATING CONNECTOR P/N 640440-2
PIN 1) -
PIN 2) +
OUTPUT:
TB2
6-32, 4 PIN TERMINAL BLOCK 0.375
[9.53mm]CTR
AN OPTIONAL BUS BAR WITH 10-32
SCREWS ON HIGH-CURRENT MODELS
IS AVAILABLE BY ADDING -B TO
MODEL NUMBER
PINS 1-2) +Vout
PINS 3-4) RETURN
16A MAXIMUM RECOMMENDED
CURRENT PER CONNECTOR PIN.
MAX. SCREW PROTRUSION ABOVE
CHASSIS =0.120” [3.05MM].
OPTIONAL: COVER/FAN ASSEMBLY #09-250CF
CAN BE INCLUDED BY ADDING -C TO
MODEL NUMBER
WEIGHT: 2.9 LBS. [1.32 kg] MAX.
TOLERANCES: X.XX=0.030 [0.76mm]
X.XXX+0.010 [0.25 mm]
Commercial
Model
Medical
Model
RoHS
Sux*
Output No.
Output
Voltage
Adjustment
Output
Maximum (A)
Output
Maximum (B)
OVP Setpoint
Total
Regulation
Notes
GPFC250-3.3 GPFM250-3.3 G 1 3.3 V ±5% 36 A 50 A 6.2 ± 0.6 V 2% C
GPFC250-5 GPFM250-5 G 1 5.1 V ±5% 36 A 50 A 6.2 ± 0.6 V 2% C
GPFC250-12 GPFM250-12 G 1 12 V ±5% 15 A 21 A 14 ± 1.1 V 2% C
GPFC250-15 GPFM250-15 G 1 15 V ±5% 12 A 16.7 A 18.5 ± 1.5 V 2% C
GPFC250-24 GPFM250-24 G 1 24 V ±5% 7.5 A 10.5 A 28 ± 2.5 V 2% C
GPFC250-28 GPFM250-28 G 1 28 V ±5% 6.5 A 9 A 34 ± 2.8 V 2% C
GPFC250-48 GPFM250-48 G 1 48 V ±5% 3.8 A 5.3 A 55 ± 4.0 V 2% C
* Add “G” sux to part number for RoHS compliant model.
A. Continuous output rating with unrestricted convection cooling.
B. Continuous output rating with 26cfm airow or “-C option. Also one minute peak rating for convection cooled.
C. Add “-C sux for factory installed cover with fan option.

GPFC250-12G

Mfr. #:
Manufacturer:
Description:
Switching Power Supplies 250W 12V @ 15A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union