Ground modular terminal block-BSLK 16-0810012
Technical data
Dimensions
Height NS 35/7,5 34 mm
Height NS 35/15 41.5 mm
Connection data
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section AWG/kcmil min. 20
Conductor cross section AWG/kcmil max 6
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 10 mm²
Min. AWG conductor cross section, stranded 20
Max. AWG conductor cross section, stranded 8
Conductor cross section stranded, with ferrule without plastic sleeve min. 0.5 mm²
Conductor cross section stranded, with ferrule without plastic sleeve max. 10 mm²
Conductor cross section stranded, with ferrule with plastic sleeve min. 0.5 mm²
Conductor cross section stranded, with ferrule with plastic sleeve max. 10 mm²
2 conductors with same cross section, solid min. 0.5 mm²
2 conductors with same cross section, solid max. 4 mm²
2 conductors with same cross section, stranded min. 0.5 mm²
2 conductors with same cross section, stranded max. 4 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic
sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic
sleeve, max.
6 mm²
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, max.
4 mm²
Connection method Screw connection
Stripping length 7 mm
Screw thread M4
Tightening torque, min 1.5 Nm
Tightening torque max 1.8 Nm