https://www.phoenixcontact.com/us/products/2924278
04/27/2016Page3/6
Isolation amplifier-MACX MCR-SL-NAM-2T-SP-2924278
Technical data
General
No. of channels 1
Status display Green LED (supply voltage)
LED yellow (switching state)
Red LED (line errors)
Flammability rating according to UL 94 V0
Degree of pollution 2
Overvoltage category II
Emitted interference EN 61000-6-4
Housing material PA 66-FR
Color green
Designation Input/output
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Input/output/supply, DIN rail connector
Electrical isolation
300 V
rms
(Rated insulation voltage (overvoltage category II; degree of
pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Input/supply, DIN rail connector
Electrical isolation 375 V (Peak value in accordance with EN 60079-11)
Designation Output 1/output 2
Electrical isolation
50 V
rms
(Rated insulation voltage (overvoltage category II; degree of
pollution 2, basic insulation as per EN 61010-1))
1 kV (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326-1
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada UL 508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
GL C, EMC1
Functional Safety (SIL) SIL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Evaluation criterion A
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Evaluation criterion A