A82-20500

Specifications are subject to change without notice (10.07.08) 1
Monitoring Relays
True RMS AC Current Transformer
Types A 82-10, A 82-20, A 82-30
5 types of input:
0
- 25 AAC
0
- 50 AAC
0 - 100 AAC
0 - 250 AAC
0 - 500 AAC
Output:
A 82-10: 0 - 20 mADC (source)
A 82-20: 4 - 20 mADC (sink)
A
82-30: 0 - 10 VDC
Easy interface to PLC or setpoint relays
Product Description
True RMS AC current me-
tering transformer for 25, 50,
100, 250 or 500 AAC. Out-
put current in accordance
with IEC 60381-1 (A 82-10,
A 82-20) or output voltage in
accordance with IEC 60381-2
(A 82-30).
A 82-10 and A 82-20 can be
used with relays DIB01,
PIB01, DIC01 or PIC01.
A 82-30 can be used with
DUB01, PUB01, DUB71,
DUC01 or PUC01.
All units can be directly con-
nected to a PLC. Power
supply ON is indicated by a
green LED on the side of the
housing.
Type
Output
Input current
Ordering Key
Type Selection
Input current Output Type no.
25 AAC 0 - 20 mA A 82-10 25
50 AAC 0 - 20 mA A 82-10 50
100 AAC 0 - 20 mA A 82-10 100
250 AAC 0 - 20 mA A 82-10 250
500 AAC 0 - 20 mA A 82-10 500
25 AAC 4 - 20 mA A 82-20 25
50 AAC 4 - 20 mA A 82-20 50
100 AAC 4 - 20 mA A 82-20 100
250 AAC 4 - 20 mA A 82-20 250
500 AAC 4 - 20 mA A 82-20 500
25 AAC
0 - 10 V
A 82-30 25
50 AAC 0 - 10 V A 82-30 50
100 AAC 0 - 10 V A 82-30 100
250 AAC 0 - 10 V A 82-30 250
500 AAC 0 - 10 V A 82-30 500
Input Specifications
A 82-10/20/30 25 A 82-10/20/30 50 A 82-10/20/30 100 A 82-10/20/30 250 A 82-10/20/30 500
Cur
r
ent range
0 - 25 AAC
0 - 50 AAC 0 - 100 AAC
0 - 250 AAC
0 - 500 AAC
Max. current (continuously) 600 AAC 600 AAC 600 AAC 600 AAC 600 AAC
Max. overload curr
ent
(t = 30 s) 3000 AAC
3000 AAC 3000 AAC
3000 AAC 3000 AAC
Rated insulation voltage
Input - output 1000 V
AC
rms
1000 VAC
rms
1000 VAC
rms
1000 VAC
rms
1000 VAC
rms
Overvoltage category IV (IEC 60664) IV (IEC 60664) IV (IEC 60664) IV (IEC 60664) IV (IEC 60664)
Dielectric str
ength
Dielectric voltage
6 kVAC
r
ms
6 kV
AC
r
ms
6 kV
AC
r
ms
6 kV
AC
r
ms
6 kV
AC
r
ms
Rated impulse withstand volt. 12 kV 12 kV 12 kV 12 kV 12 kV
(1.2/50
µ
s)
(1.2/50
µ
s)
(1.2/50
µ
s) (1.2/50 µs) (1.2/50 µs)
A 82-10 50
2 Specifications are subject to change without notice (10.07.08)
A 82-10, A 82-20, A 82-30
Output Specifications
Rated insulation voltage (cable) 250 VAC
rms
Output
A 82-10 0 - 20 mADC
A
82-20 4 - 20 mADC
A
82-30 0 - 10 VDC
Power supply (loop voltage)
A 82-10, A 82-20 10 - 40 VDC
A
82-30 18 - 40 VDC
T
olerance of output current
@
50 Hz A 82-10 ±2%
A 82-20 ± 2%
Tolerance of output voltage
@ 50 Hz A 82-30 ±2%
Temperature variation ±400 ppm/ºC
Frequency range 40 Hz -1 kHz
Frequency variation 10 ppm/Hz
Maximum output current
A 82-10, A 82-20 30 mADC
Maximum output voltage
A 82-30
15 VDC
Minimum output load
A 82-30 10 k
General Specifications
Power ON delay < 2 s
Reaction time T < 200 ms
Indication for
Power supply ON LED, green
Environment
D
egree of protection IP 40
P
ollution degree 3 (IEC 60664)
O
perating temperature -20° to 50ºC (-4° to +122 ºF)
Housing
Dimensions 95 x 67.5 x 20 mm
Material ABS
W
eight
A 82-10, A 82-30 300 g
A 82-20 270 g
Connection cable
A 82-10, A 82-30 2 m, 3 x 0.25 mm
2
A 82-20
2 m, 2 x 0.25 mm
2
Approval UL
CE marking Yes
EMC Electr
omagnetic Compatibility
Immunity According to EN 61000-6-1
(tolerance of output
current/voltage: ± 2%)
According to EN 61000-6-2
(tolerance of output
current/voltage: ± 5%)
Emission According to EN 61000-6-3
A 82-10 and A 82-20 ar
e
true RMS current metering
transformers with standard
source/sink output 0-20 mA /
4-20 mA, whereas A 82-30
is a metering tranformer with
0-10 VDC output voltage.
This makes them very useful
as an AC cur
rent interface to
a PLC with mADC or VDC
input. Used with relays
DIB01, PIB01, DIC01, PIC01
(A 82-10, A 82-20) or
DUB01, PUB01, DUB71,
DUC01, PUC01 (A 82-30),
one or mor
e setpoints can
monitor the current and sig-
nal alar
m.
The meter
ed conductor is
drawn through the central
hole of the current metering
transformer. It is possible to
meter currents below the
nominal range by drawing
the conductor thr
ough the
hole several times. If the
conductor is drawn thr
ough
the central hole e.g. 5 times,
the transformer will register
50 A when the current in the
conductor is 10 A.
Mode of Operation
Input/Output Curve
A 82-10 ... , A 82-20 A 82-30 ...
Specifications are subject to change without notice (10.07.08) 3
Resistance/Voltage Curve
A 82-10, A 82-20, A 82-30
Wiring Diagrams (cont.)
A 82-10 ... (source)
A 82-20 ... (sink)
Wiring Diagrams
A 82-30 ...
A 82-10 ... , A 82-20
(
max. load resistance vs Power suppy - Loop voltage)
Dimensions

A82-20500

Mfr. #:
Manufacturer:
Description:
CURRENT TRANSFORMER
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet