https://www.phoenixcontact.com/pi/products/2902932
04/30/2017Page2/5
Module carrier-TC-D37SUB-AIO16-EX-PS-UNI-2902932
Technical data
Supply
Designation Power module
Note
Power supply via 2904673 TC-MACX-MCR-PTB power supply and error
signaling module.
Input voltage 24 V DC
Input voltage range 19.2 V DC ... 30 V DC
Input current ≤ 2 A
Redundant supply yes, decoupled from diodes
Polarization and surge protection Yes
Output name Switching output
Contact type 1 N/C contact (alarm = open)
Maximum switching voltage 50 V DC (0.3 A)
Fuse 2x 2.5 A on PCB, slow-blow (replaceable)
Status display 1 x red LED (error)
2x green LEDs (PWR1 and PWR2)
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C (Please observe module specifications)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Permissible humidity (operation) 5 % ... 95 % (non-condensing)
Shock 15g, according to IEC 60068-2-27
Vibration (operation) 2g, according to IEC 60068-2-6
Maximum altitude ≤ 2000 m
Dimensions
Width 242 mm
Height 170 mm
Depth 160 mm
Standards and Regulations
Shock 15g, according to IEC 60068-2-27
Designation Air clearances and creepage distances
Standards/regulations DIN EN 50178
Rated insulation voltage 50 V
Rated surge voltage 0.5 kV
Insulation Basic insulation
Flammability rating according to UL 94 V0
Vibration (operation) 2g, according to IEC 60068-2-6
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Environmental Product Compliance