http://www.phoenixcontact.de Feb 4, 2011
Drill hole spacing 168 mm
Weight 350 g
Mounting type Wall mounting
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (storage/transport) 95 %
Air pressure (operation) 80 kPa ... 106 kPa (up to 2000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP65/67
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section 24 V supply (bus logics) / Bus connection
24 V supply (bus logics) / FE 500 V AC 50 Hz 1 min
24 V supply (bus logics) / Digital outputs (actuator supply) 500 V
AC 50 Hz 1 min
Bus connection / FE 500 V AC 50 Hz 1 min
Bus connection / Digital outputs (actuator supply) 500 V AC 50
Hz 1 min
FE / Digital outputs (actuator supply) 500 V AC 50 Hz 1 min
Interface
Fieldbus system PROFIBUS-DP
Name PROFIBUS DP
Type of connection 2 M12 plug connectors, B-coded
Designation connection point Copper cable
Transmission speed 9.64 kBaud to 12 Mbaud automatic detection
12 MBit/s (Automatic baud rate detection)
Transmission physics PROFIBUS-DP-compliant copper cable
Address area assignment 1 ... 99, can be set
Number of positions 5
Power supply for module electronics
Type of connection M12 plug connectors, (A-coded)
Name U
L
Supply voltage 24 V DC
Supply voltage range 18 V DC ... 30 V DC IEC 61131-2 (including ripple)
Fieldline potential routing
Voltage supply U
L
24 V DC