https://www.phoenixcontact.com/pi/products/2800624
04/30/2017Page2/4
Type 2 surge protection plug-VAL-MS 1000DC-PV-ST-2800624
Technical data
General
Installation location Inside
Accessibility Accessible
Installation location of the disconnect device Internal
Mounting type On base element
Color jet black RAL 9005
Housing material PA 6.6-FR
Degree of pollution 2
Flammability rating according to UL 94 V-0
Design Male
Surge protection fault message optical
Protective circuit DC voltage side (DC)
Maximum continuous operating voltage U
CPV
585 V DC
Open circuit voltage U
OCSTC
≤ 485 V DC
Short-circuit current rating I
SCPV
1000 A
Continuous operating current I
CPV
< 20 µA
Standby power consumption P
C
≤ 25 mVA
Nominal discharge current (8/20) µs 15 kA
Maximum discharge current I
max
(8/20) µs
40 kA
Voltage protection level U
p
≤ 1.9 kV
Residual voltage U
res
≤ 1.9 kV (at I
n
)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Response time t
A
≤ 25 ns
Insulation resistance R
iso
> 5 GΩ (at 500 V DC)
UL specifications
SPD Type 4CA
Maximum continuous operating voltage MCOV (L+) - G 1170 V DC
Nominal voltage 970 V DC
Mode of protection (L+) - G
Power distribution system 1
Measured limiting voltage MLV (L+) - G 1980 V
Nominal discharge current I
n
(L+) - G
10 kA
Standards and Regulations
Standards/regulations EN 50539-11 2013
Environmental Product Compliance