PLC-…-EIK 1-SVN 24…
102895_04_en PHOENIX CONTACT 2
Ordering Data
Technical Data
PLC Electronic Sensor Terminal Block for NAMUR Proximity Sensors
Description Type Order No. Pcs./Pck.
PLC electronic sensor terminal block for NAMUR proximity sensors
Positive switching, with screw connection PLC-SC-EIK 1-SVN 24P/P 2982663 10
Positive switching, with spring-cage connection PLC-SP-EIK 1-SVN 24P/P 2982676 10
Negative switching, with screw connection PLC-SC-EIK 1-SVN 24M 2982595 10
Negative switching, with spring-cage connection PLC-SP-EIK 1-SVN 24M 2982605 10
Accessories
Description Type Order No. Pcs./Pck.
Double-level terminal block, with pre-assembled resistors UKK 5-2R/NAMUR 2941662 50
Insulating plate PLC-ATP BK 2966841 25
For other accessories such as power terminal blocks and plug-in bridges please consult the INTERFACE catalog and www.phoenixcontact.com.
Power Supply
Nominal input supply voltage U
VN
24 V DC ±20%
Typical input current at U
VN
14 mA, approximately
Transmission frequency f
limit
350 Hz, approximately
Input circuit Green LED, protection against polarity reversal, surge protection
The PLC-ATP BK insulating plate should be used in the following cases: always fit at the start and end of a PLC terminal strip for voltages
greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules (FBST 8-PLC... or FBST 500... can be used for
potential bridging) and for safe isolation between adjacent modules.
Control Circuit
Non-load voltage 8.2 V DC ±10%
Switching point according to EN 60947-5-6
In conductive state
In disabling state
In the event of short circuit
In the event of wire break
≥ 2.1 mA
≤ 1.2 mA
20 mA, approximately
12 mA, approximately
Switching hysteresis 0.2 mA, approximately
Internal resistance 1 kΩ, approximately
Protective circuit Surge protection
Alarm Output
Operating voltage range (negative switching) 3 V DC ... 33 V DC
Operating voltage range (positive switching) U
VN
- 1.5 V
Limiting continuous current 100 mA
Voltage drop at maximum limiting continuous current ≤ 1.5 V
Output circuit Red LED, surge protection
Signal Output
Limiting continuous current 50 mA
Voltage drop U
R
at maximum limiting continuous current ≤ 1.5 V
Output voltage (positive switching)
In conductive state
In disabling state
≤ 100 mV
U
VN
- U
R
Output voltage range (negative switching) 3 V DC ... 33 V DC
Output circuit Surge protection