NAP-16-101-DXE

NA-4
NAP series
High-voltage pulses high-attenuation type
NAP -10 -472 -O
Ordering information
1 Model Name
2 Rated Current
3 Line to ground capacitor code:See table 1.1.
table1.1 Line to ground capacitor code
Code
Leakage Current
(Input 125/250V 60Hz)
Line to ground
capacitor
(nominal value)
000
5
A/ 10 A max Not Provided
101
12.5
A/ 25 A max 100pF
221
25
A/ 50 A max 220pF
331
37.5
A/ 75 A max 330pF
471
50
A/ 100 A max 470pF
681
75.5
A/ 150 A max 680pF
102
0.13
mA/
0.25mA max 1000pF
222
0.25
mA/
0.5 mA max 2200pF
332
0.38 mA/ 0.75mA max 3300pF
472
0.5
mA/
1.0 mA max 4700pF
*
When the line to ground capacitor code is
different, the attenuation characteristic is
different.
4 Options
D
:DIN rail installation type
*
The dimensions change when the option is set.
Refer to External view.
R
1 2 3 4
Features of NAP series
Circuit Diagram Derating Curve
LINE
Case
: Mounting Plate
1
2
4
3
CY
CY
CY : Line to ground capacitor
LOAD
High-voltage pulses high-attenuation type
- Single Phase 250 VAC
- Push down type terminal block
9050 60 70 80
20
0
-4040-30-20
100
80
60
40
55
Ambient Temperature [C]
Load Factor [%]
Specifications
No. Items NAP-04-472 NAP-06-472 NAP-10-472 NAP-16-472 NAP-20-472 NAP-30-472
1 Rated Voltage[V] AC 1
f
250 / DC250
2 Rated Current[A] 4 6 10 16 20 30
3 Test Voltage (Terminal-Mounting Plate) 2,500 VAC (Cutoff Current = 20mA), 1minute at room temperature and humidity
4 Isolation Resistance (Terminal-Mounting Plate) 500 VDC 100M
W
min at room temperature and humidity
5 Leakage current 125/250V 60Hz 0.5mA/1.0mA max
6 Voltage drop 1.0V max
7 Safety agency approval temperatures -25 to +85
C
(Refer to Derating Curve)
8 Operating temperature -40 to +85
C
(Refer to Derating Curve)
9 Operating humidity 20 to 95%RH (Non condensing)
10 Storage temperature/humidity -40 to +85
C
/20 to 95%RH (Non condensing)
11 Vibration 10 to 55Hz, 19.6m/s
2
(2G), 3min. Period, 1hour each X, Y and Z axis
12 Impact 196.1m/s
2
(20G), 11ms Once each X, Y and Z axis
13 Safety agency approvals UL1283, CSA C22.2 No.8 (C-UL), DIN EN60939 VDE0565 Teil3-1, ENEC (At only AC input)
14 Case size (without projection) /Weight
53
X
41
X
92 mm [2.09
X
1.61
X
3.62 inches] (W
X
H
X
D) /300g max (Option : -D refer to external view)
DIN rail installation type is optionThe terminal cover is retracted inside the unit
NA-5
NAH,NAC,NAM,NAP series
Mounting Plate
Terminal cover
2-Protection Earth
6-M4
2-f4.8
Name Plate
Tolerance : ±1 [±0.04]
Weight : 300g max
Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
Case : PBT
Dimensions in mm, [ ]=inches
Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max
Output
Terminal
Input
Terminal
Output
Terminal
Mounting Hole
Input
Terminal
82
±
0.5
77
15
45
±
0.5
(2)
41
53
[2.09]
[1.61]
[0.08]
[1.77]
[0.47]
[0.59]
92
Terminal cover
Closed the terminal cover
12
8
27
(2.5)
[0.1]
[3.62]
[3.23]
[0.19]
[3.03]
[1.06]
[0.31]
As this product is adopted push-down type terminal block, this appearance is as follows.
1The terminal cover is retracted inside the unit.
2The screws for connecting the terminals are held in the up right position.
¡
Note when installing the EMI/EMC
Filter on a DIN rail.
When the EMI/EMC Filter is grounded through
the DIN rail, the proper noise attenuation may not
be achieved.
Be sure to connect the protection earth (PE) of
the EMI/EMC Filter body to the earth.
It can connect the ground to either one only.
6-M4
Name Plate
Output
Terminal
Output
Terminal
7
(9)
(11)92
53
41
(2)
12
15
77
Tolerance : ±1 [±0.04]
Weight : 300g max
Mounting Plate : Iron (surface finishing:nickel plating) t=1.0 [0.04]
Case : PBT
Dimensions in mm, [ ]=inches
Terminal block screw tighting torque M4:1.6N-m (16.9kgf-cm) max
(2.5)
8
27
2-Protection Earth
Mounting Plate
Terminal cover
DIN rail
Input
Terminal
Input
Terminal
Terminal cover
Closed the terminal cover
[2.09]
[0.47]
[0.59]
[0.35]
[0.28]
[0.08]
[1.61]
[0.1]
[3.62]
[0.43]
[3.03]
[1.06]
[0.31]
Standard Type
DIN rail installation Type
Name Plate
DIN rail
External view

NAP-16-101-DXE

Mfr. #:
Manufacturer:
Cosel
Description:
AC Power Line Filters Power Line Filters AC 1-250 / DC250 16A 12.5 uA/ 25 uA max