4
Thermal (T- and TA-Line)
T11-211
www.schurter.com /PG17_20
Circuit Breakers
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C] Correction factor
-5 0.87
0 0.90
+10 0.95
+23 1.00
+30 1.04
+40 1.10
+50 1.15
+60 1.20
Example: Rated current = 5 A; Environmental temperature = 40 °C; --> Correction factor =
1.1; Resulting current = 5.5 A --> Fount to next higher rated current: 6 A
Time-Current-Curves
Time in Seconds
10`000
1,05
60
1085432
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0,3
0,2
0,1
30
20
10
5
1
< 6,5 A
>
6,5 A
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
T11|-|1|2|3|A|B|-|1.23|
The characters are placeholders for the correspondingly keys of selections from the key tables.
T11|-| 1 |2|3|A|B|-|1.23| = Mounting
Mounting Configuration
key
Threaded neck type 6 mm 2
T11
|-|1| 2 |3|A|B|-|1.23| = Actuation Type
Actuation Type Configuration
key
Reset type 1
T11|-|1|2| 3 |A|B|-|1.23| = Terminal
Terminal Configuration
key
Quick connect terminal 6.3x0.8mm 1
T11
|-|1|2|3| A |B|-|1.23| = Shunt terminal
Shunt terminal Configuration
key
Shunt terminal N