MB1216

111-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
MB Series
Features
u High Attenuation Wide Band Two Stage Filter
u Screw Terminals with Cover
u Low Profi le, Metal Case
6A to 36A, 250VAC EMI Filters
Model MB1206 MB1210 MB1216 MB1220 MB1236
Rated Voltage (AC,DC) V 250V
Rated Current (AC,DC) (1) A 6 10 16 20 36
Test Voltage V 2500V (20mA) at 25°C, 70% RH
(terminal to case, AC 1 min.)
Isolation Resistance 100M Ohms min. at 25°C, 70% RH
(terminal to case, 500VDC)
Leakage Current - 125V, 60Hz =0.5mA max.; 250V, 60Hz =1mA max.
DC Resistance m 140 50 34 20 9
Temperature Rise °C 40°C max.
Operating Temperature (1) °C -25 to +85°C
Operating Humidity % 30% to 95% RH (non-condensing)
Storage Temperature °C -40 to +85°C
Storage Humidity % 10% to 95% RH (non-condensing)
Vibration - Sweep:10-55-10Hz (1min.), Amplitude 1.5mm X, Y, and Z axes, 2 hours each
Safety Standard - UL1283, CSA C22.2 No.8 (C-UL), VDE0565 Teil3, Teil3A2, and EN133200 (VDE)
Specifi cations
Notes:
(1) Value at Ta ≤35°C. Refer to the derating curve at Ta > 35°C.
Last time buy - June 1, 2014
121-800-526-2324 • www.us.tdk-lambda.com/lp/
Revision A3: May 2013
MB Series
For Additional Information, please visit
us.tdk-lambda.com/lp/products/mb-series.htm
Circuit
Derating
MB1206MB1210MB1216MB1220MB1236
Frequency (MHz)
Attenuation (dB)
MB1206MB1210MB1216MB1220MB1236
Frequency (MHz)
Attenuation (dB)
Typ. Insertion Loss, Symmetrical Typ. Insertion Loss, Asymmetrical
Outline Drawing
A
D
E
B
C
Ø4.8mm (4 on MB1236)
Last time buy - June 1, 2014
Model A B C D E Weight (g)
MB1206 100 23.6 47 6.5 4 190
MB1210 107 26 47 6.5 4 220
MB1216 117 30 47 6.5 4 310
MB1220 151 35 52 6.5 4 530
MB1236 151 35 67 7.5 6.5 660
Dimensions Table