Inductive Proximity Sensors
(Wiring Schematic)
3 Wire DC PNP – Normally Open (1) - - - - -
PNP – Normally Closed (1) - - - - -
PNP – Selectable (4) - - - - -
NPN – Normally Open (2) - - - - -
NPN – Normally Closed (2) - - - - -
NPN – Selectable (5) - - - - -
2 Wire DC Normally Open (6) IMM423010C IMM453015C IMN423010M12 IMN453015M12 IMM623010C
Normally Closed (6) IMM433010C IMM463015C IMN433010M12 IMN463015M12 IMM633010C
2 Wire AC
- - - -
Normally Closed (7) - - - -
Mating cables / connectors
Form M30 Shielded M30 Non-Shielded M30 Shielded M30 Non-Shielded M30 Shielded
Nominal Sensing Distance (Sn) 10mm 15mm 10mm 15mm 10mm
Housing Material
Nickel Plated Brass
Termination Type 2.0 Meter Cable 2.0 Meter Cable M12 Connector M12 Connector 2.0 Meter Cable
Min / Max Supply Voltage 10 to 30Vdc 20 to 220 Vac
Max. Load Current (Ir) 100mA 400 mA
Max ripple factor (Vr)
≤ 10%
-
Voltage Drop (Ud)
Power Consumption (Io) ≤ 0.7mA ≤ 2.5mA
Switching Frequency (Hz) 200 Hz 200 Hz 200 Hz 200 Hz 20 Hz
Repeatability < 2% nominal sensing distance
Hysteresis ≤ 10% Sn
Short Circuit Protection Yes No
Output LED Yes Yes
Operating Temperature -25 to +70 C
IP Rating IP67 (with connector mounted)
Wiring Diagram
≤ 7.5 Vdc ≤ 4.5Vac
For Technical Assistance and / or Customer Service, call 800/677-5311, www.crouzet-usa.com
M30 Inductive Proximity Sensors
Standard Length
“Mini's”
Extended Sensing
3 Wire DC
2 Wire DC
2 Wire AC