cui.com
date 01/17/2013 │ page 3 of 7CUI Inc │ SERIES: VDRS-150 │ DESCRIPTION: AC-DC DIN RAIL
SAFETY & COMPLIANCE
parameter conditions/description min typ max units
isolation voltage
input to output for 1 minute
input to case for 1 minute
output to case, output to DC OK for 1 minute
4,242
2,121
707
Vdc
Vdc
Vdc
isolation resistance
input to output, input to case,
output to case, 500 Vdc
100
MΩ
safety approvals UL 508, TUV EN 60950-1
EMI/EMC
2
EN 55022 (CISPR22) Class B, EN 61000-3-(2, 3), EN 61000-4-(2,3,4,5,6,8,11) ENV 50204, EN 55024,
EN 61000-6-2 (EN50082-2), EN 61204-3, heavy industry level, criteria A, meet SEMI F47
RoHS compliant yes
Note: 2. The power supply is considered a component which will be installed into a fi nal equipment. The fi nal equipment must be re-confi rmed that it still
meets EMC directives.
ENVIRONMENTAL
parameter conditions/description min typ max units
operating temperature -10 70 °C
storage temperature -40 85 °C
operating humidity non-condensing 20 90 %
storage humidity 10 95 %
vibration (10 ~ 500 Hz, 1 hour per axis, 3 hours total) 2 Grms