Distribution block, Basic terminal block with supply, nom. voltage: 500 V, nominal current: 24 A, connection
method: Push-in connection, Push-in connection, number of connections: 13, cross section:0.14 mm²-4
mm², AWG:26-12, width: 40.6 mm, height: 21.2 mm, color: red, mounting type: for snapping onto a DIN rail
adapter, Adapter plate
Why buy this product
Time savings of up to 80%, thanks to ready-to-mount blocks without manual bridging
Time-saving conductor connection, thanks to tool-free Push-in direct connection technology
Clear wiring, thanks to eleven different color variants
Flexible use, thanks to DIN rail mounting, direct mounting or adhesive mounting
Space savings of up to 50% on the DIN rail, thanks to transverse mounting
Key Commercial Data
Packing unit 8 STK
GTIN
GTIN 4055626392479
Technical data
General
Note
Notes on operation The blocks can be bridged with one another via the
conductor shaft. For corresponding plug-in bridges, see accessories
Number of levels 1
Number of connections 13
Potentials 1
Nominal cross section 2.5 mm²
Nominal cross section feed-in 6 mm²
Color red
Insulating material PA
Flammability rating according to UL 94 V0
Rated surge voltage 6 kV
Degree of pollution 3
https://www.phoenixcontact.com/pi/products/3273356
08/18/2018Page2/5
Distribution block-PTFIX 6/12X2,5 RD-3273356
Technical data
General
Overvoltage category III
Insulating material group I
Maximum power dissipation for nominal condition
1.31 W (the value is based on one connection block and is multiplied
according to the pin assignment)
Maximum load current 24 A
Nominal current I
N
24 A
Nominal voltage U
N
500 V
Maximum load current 57 A (with 10 mm² conductor cross section)
Nominal current I
N
41 A (with 6 mm² conductor cross section)
Nominal voltage U
N
500 V
Open side panel No
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Result of thermal test Test passed
Proof of thermal characteristics (needle flame) effective duration 30 s
Oscillation, broadband noise test result Test passed
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum Service life test category 2, bogie-mounted
Test frequency
f
1
= 5 Hz to f
2
= 250 Hz
ASD level
6.12 (m/s
2
)
2
/Hz
Acceleration 3.12 g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Shock test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
Shock form Half-sine
Acceleration 30g
Shock duration 18 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Dimensions
Width 40.6 mm
Length 28.2 mm
Height 21.2 mm
Connection data
Feed-in connection Feed-in stage
Connection method Push-in connection
Connection in acc. with standard IEC 60998-2-2
Conductor cross section solid min. 0.14 mm²
https://www.phoenixcontact.com/pi/products/3273356
08/18/2018Page3/5
Distribution block-PTFIX 6/12X2,5 RD-3273356
Technical data
Connection data
Conductor cross section solid max. 4 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Min. AWG conductor cross section, flexible 26
Max. AWG conductor cross section, flexible 14
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
Stripping length 8 mm ... 10 mm
Internal cylindrical gage A3
Connection method Push-in connection
Connection in acc. with standard IEC 60998-2-2
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 10 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 8
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 6 mm²
Min. AWG conductor cross section, flexible 20
Max. AWG conductor cross section, flexible 10
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 6 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 6 mm²
2 conductors with same cross section, stranded, TWIN ferrules with
plastic sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with
plastic sleeve, max.
1.5 mm²
Stripping length 10 mm ... 12 mm
Standards and Regulations
Connection in acc. with standard IEC 60998-2-2
IEC 60998-2-2
Flammability rating according to UL 94 V0
Environmental Product Compliance
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values