TechnischeKennwerte
HARTING Electric GmbH & Co. KG|Wilhelm-Harting-Straße1|D-32339Espelkamp
Fon: +49 57 72 47-97100 | Fax: +49 57 72 47-124
Internet:www.HARTING.com|E-Mail:HARTING.Electric@HARTING.com
2011-09-09
Features Technicalcharacteristics
Specications DINEN60664-1
DINEN6061984
Inserts
Numberofcontacts 1/4
Electricaldataaccd.to
DINEN61984
Powercontacts 70A1000V8kV3
Rated current 70 A
Ratedvoltage 1000V
Ratedimpulsevoltage 8kV
Pollutiondegree 3
Signalcontacts 16A400V6kV3
Rated current 16 A
Ratedvoltage 400V
Ratedimpulsevoltage 6kV
Pollutiondegree 3
Insulation resistance ≥ 10
10
Ω
Material Polycarbonate
Limitingtemperatures -40°C...+125°C
Flammabilityaccd.toUL94 V0
Mechanicalworkinglife ≥500matingcycles
PowerContacts
Material Copperalloy
Surface
-hard-silverplated 3µmAg
Contact resistance ≤ 0.5 mΩ
Axial screw terminal
-geometricwiregauge 6 ... 22 mm²
- AWG 8 ... 4
-Hexagonaldrive SW2.5
Tighteningtorque
Strippinglength
SignalContacts
Material Copperalloy
Surface
-hard-silverplated 3µmAg
-hard-goldplated 2µmAgover3µmNi
Contact resistance ≤ 1 mΩ
Crimpterminal
- mm² 0.14 ... 4 mm²
- AWG 26 ... 12
• onecontact(70A)forpowercircuits
• fourcontacts(16A)forsignalcircuits
• CombinationofPowerandsignalcontactsinone
modul
Han-Modular
®
70 A Hybrid Module
mm
2
6 10 16 22
mm 11
+1
11
+1
11
+1
12.5
+1
mm
2
6 10 16 22
Nm 2 3 4 5