2-5700-IG1-P10-14A

Thermal Overcurrent Circuit Breakers 2-5000/2-5700-...
www.e-t-a.de
1629 1
1
Description
Typical applications
Ordering information
Preferred types
Technical data
Single pole thermal circuit breaker with press-to-reset, tease-free,
trip-free, snap action mechanism. Type 2-5000 is available with optional
manual release (-H), type 2-5700 can be supplied as a push-push
switch/circuit breaker (R-type TO CBE to EN 60934 in press-to-reset
configuration; M-type when fitted with manual release -H; S-type
with push-push operation). Fitted with flange or threadneck for panel
mounting. Options include an additional unprotected circuit tap (-A3).
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, battery chargers, power supplies,
appliances, machinery, extra low voltage systems.
2-5000-... 2-5700-...
Type No.
2-5000 flange mounting
2-5700 threadneck panel mounting
Threadneck design – type 2-5700 only
iG1 moulded threadneck 3/8“-27UNS-2A with metal hexnut and
plastic knurled nut (hardware bulk shipped with 5 pcs plus)
iG2 moulded threadneck M12x1 with metal hexnut and plastic
knurled nut (hardware bulk shipped with 5 pcs plus)
Terminal design
P10 blade terminals 6.3-0.8 mm (QC .250)
K10 screw terminals M4x6
Manual release (optional)
H manual release facility (type 2-5000 only)
DD push to release/push to reset (type 2-5700 only)
Current ratings
0.05...25 A
2-5700 - iG1 - P10 - DD - 8 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Approvals
For further details please see chapter: Technical Information
Voltage rating AC 250 V; DC 28 V
(UL: AC 250 V; DC 50 V)
Current rating range 0.05...25 A
Typical life AC 250 V / DC 28 V:
0.05...16 A 5,000 operations at 2 x I
N
, inductive
17...25 A 5,000 operations at 2 x I
N
, resistive
Ambient temperature -20...+60 °C (-4...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.05...2.5 A 8 x I
N
3...5 A 20 x I
N
6...12 A 200 A
(higher interrupting capacity
available to special order)
13...25 A 300 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...20 A AC 250 V 2,000 A
0.05...25 A DC 50 V 2,500 A
(higher values upon request)
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 8 g (57-500 Hz) ± 0.61 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock 25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 29 g
Preferred types Standard current ratings (A)
1 2 3 4 5 6 8 10 12 15 16 20 25
2-5700-IG1-P10-
x x x x x x x x x x x x x
2-5700-IG1-P10-DD
x x x x x x x x x x x
2-5700-IG2-P10-
x x x x x x x x x x x
2-5700-IG2-P10-DD
x x x x x x x x x x x
Authority Standard Rated voltage Current ratings
VDE IEC/EN 60934 AC 250 V
DC 28 V
0.05 A…25 A
0.05 A…25 A
UL UL 1077 AC 250 V
DC 50 V
0.05 A…20 A
0.05 A…25 A
CSA C22.2 No 235 AC 250 V
DC 50 V
0.05 A…20 A
0.05 A…25 A
CQC GB 17701 AC 250 V
DC 28 V
0.05 A…25 A
0.05 A…25 A
Thermal Overcurrent Circuit Breakers 2-5000/2-5700-...Thermal Overcurrent Circuit Breakers 2-5000/2-5700-...
www.e-t-a.de
16292
1
mounting area
max. 2.5
operating area
mounting area
max .098
2-5700-P10
2-5000-P10
A
1432
1432
A
25
25
max. 2.5
11
max .098
operating area
.039
.039
.984
.984
iG1=ø9.6-0.1
iG2=ø12.2-0.1
iG1=8.9-0.1
iG2=11.5-0.1
blade terminal
DIN 46244-A6.3-0.8
(QC .250)
ø6.5
5
SW 14
iG1=8.8
iG2=11.3
D-shaped threadneckcurrent rating in A for standard
(-DD version without push button marking)
A
1432
iG1=
3
/
8
-27UNS-2A tightening torque max. 1 Nm
3
/
8
iG2=M12x1 tightening torque max. 1.5 Nm
OFF
ON
1046.5
10.4
19.8
29
14.5
.394
.409
.780
1.14
.551
.256
.571
.886
.650
1.83
16.5
22.5
mounting hole
iG1=.378
-.004
iG2=.480-.004
iG1=.350-.004
iG2=.453-.004
iG1=.346
iG2=.445
current rating in A
5
18.5
ø4.5
40
50
A
1432
ø9.5
5
12.2
18.2
OFF
ON
10.4
44
19.8
31
ø13.5
7
14.5
blade terminal DIN 46244-A6.3-0.8
(QC .250)
.374
.480
1.73
.409
.780
1.22
1.57
1.97
.177
.728 .717
.531
.276
.571
.197
2-5700-P10
2-5000-P10
1432
flat head screw M4x6 ISO1580
tightening torque 1.2 Nm
10.4
.409
-K10
Dimensions
Terminal design
Installation drawings
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
Standard current ratings and typical internal resistance values
Current
rating (A)
Internal
resistance (Ω)
Current
rating (A)
Internal
resistance (Ω)
0.05 280 3 0.1
0.08 100 3.5 0.06
0.1 110 4 0.06
0.2 29 4.5 0.05
0.3 14 5 0.05
0.4 7 6 0.02
0.5 4.9 7 0.02
0.6 3.4 8 0.02
0.7 2.5 10 < 0.02
0.8 1.8 12 < 0.02
1 1.2 13 < 0.02
1.2 0.8 15 < 0.02
1.5 0.6 16 < 0.02
1.8 0.4 20 < 0.02
2 0.3 22 < 0.02
2.5 0.2 25 < 0.02
Thermal Overcurrent Circuit Breakers 2-5000/2-5700-...
www.e-t-a.de
1629 3
1
Thermal Overcurrent Circuit Breakers 2-5000/2-5700-...
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
Ambient temperature °F
°C
-4
-20
+14
-10
+32
0
+73.4
+23
+104
+40
+122
+50
+140
+60
Derating factor
0.76 0.84 0.92 1 1.08 1.16 1.24
1
2
Internal connection diagrams
Typical time/current characteristics at +23 °C/+73.4 °F
12468102040
Trip time in seconds
... times rated current
0.05 - 2.7 A
2.8 - 23 A
10000
1000
100
10
1
0.1
25 A
This is a metric design and millimeter dimensions take precedence (
mm
)
inch

2-5700-IG1-P10-14A

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union