GPFC125DG

52
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com
GPFC125 Commercial/GPFM125 Medical
125 Watt Global Performance Switchers
Ac Input
90-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current 2A at 90 Vac, 60 Hz with full rated load.
Input current harmonic content meets the requirements of
IEC1000-3-2. Active circuitry provides high power factor as
listed at .96 min., .99 typical. All data taken with full output
loading.
DC Output Power
125 W with 150 LFM of air, 50 W convection cooled, 80 W
convection cooled with unit mounted to min. 12 x 12 x .125 in.
thick aluminim plate. Peak ratings are for 60 s maximum
duration, 10% duty cycle. With optional cover installed,125 W,
200 LFM airflow is required(-C suffix).
Inrush Current
Inrush 240 Vac is less than 37 A, averaged over the first ac
half-cycle under cold start conditions. Limiting provided by
internal thermistors.
Input Protection
Internal ac fuse provided on all models. Fuse does not blow on
overload or short circuit — fuse blows only if a catastrophic
failure occurs in the unit.
Efficiency
72 to 85% at full rated load. Depending upon model and load
distribution.
Minimum Load
Supply will function with no load on any output. To maintain
regulation with full load on V2, 3 and 4 output V1 requires a
minimum load of (2A + V4 current). Lower minimum load may be
obtained if less then full load is drawn from auxiliary outputs.
Overload Protection
Fully protected against short circuit and output overload. Total
output power limited to approximately 150 Watts. Cycling type
limits on output 1, 2 & 3, linear fold back on output 4. Recovery
after fault is automatic.
Overvoltage Protection
Built in on all models - See Output table for individual model
output limits.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz Bandwidth, differential mode.
Transient Response
500 ms typical response time for return to within 0.5% of final
value for a 50% load step change, i/t< 0.2 A ms. Maximum
voltage deviation is 3.5%.
Temperature Coefficient
0.03% / °C typical on all outputs.
Remote Sense
Provided as a standard feature on V1 of all models.
Temperature Range
0 to 50 °C at full rated output power. For operation above 50 °C,
derate output power and current by 2.5 % per °C.
Altitude
Operating: -500 to 10,000 ft. MSL
Non-Operating -500 to 40,000 ft MSL
Shock and Vibration
All models are designed to meet the following specifications;
Random Vibration -
Operating: 0.003 g
2
/Hz, 1.5 g
rms
overall, 3 axes, 10 min. / axis
Non-Operating: 0.026 g
2
/Hz, 5.0 g
rms
overall, 3 axes, 1 hr. / axis
Shock -
Operating: Half-sine, 20
g
pk
, 10 ms, 3 axes, 6 shocks total
Non-Operating: Half-sine, 40 g
pk
, 10 ms, 3 axes, 6 shocks total
EMI/EMC Compliance
All models include built-in EMI filtering to meet the EMC
requirements below.
EMI SPECIFICATIONS COMPLIANCE LEVEL
Conducted Emissions-GPFC125 EN55022, Class B; FCC Class B
Conducted Emissions-GPFM125 EN55011,Class B; FCC Class B
Static Discharge EN61000-4-2, 6 kV contact 8 kV air
RF Field Susceptibility EN61000-4-3, 3V/meter
Fast Transients / Bursts EN61000-4-4, 2 kV, 5 kHz
Surge Susceptibility EN61000-4-5, 1 kV diff., 2 kV com.
Conducted RF Susceptibility EN61000-4-6, 3V
Voltage Sags & Surges EN61000-4-11
Line Frequency Harmonics EN61000-3-2 Class A
Commercial Safety Approvals
All models are approved to UL1950, CSA22.2 No. 950-95,
IEC950, EN60950. CB certificate available. Exceeds FCC and
CISPR22 Class B conducted emissions requirement
Medical Safety Approvals
All models are Certified to be in compliance with the applicable
requirements of UL2601, CSA 22.2 No. 601.1-M90, IEC 601-1
(1988), EN 60601-1: 1990. CB certificate available.
Leakage Current
The maximum leakage current is as follows:
Test Condition Normal Single Fault
132 Vac @ 60 Hz input 70 µA 120 µA
264 Vac @ 50 Hz input 130 µA 240 µA
FEATURES:
Compact 125 watt multiple output
Power density of 4 watts per cubic inch
Power Factor Correction to meet EN61000-3-2
Small package 6.00 x 3.5 x 1.5 inches
Conducted EMI exceeds FCC Class B and CISPR 22
Class B (Commercial models) and CISPR 11 Class B
(Medical models)
Commercial approved to UL1950, IEC950, CSA22.2
No. 950 and EN60950.
Medical approved to UL2601-1, IEC601-1, CSA22.2
No. 601.1, EN60601-1
marked to LVD
SPECIFICATIONS:
53
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 • 805-486-4565 • FAX 805-487-8911 • www.condorpower.com
GPFC125 Commercial/GPFM125 Medical 125 Watt Multiple Output
INPUT: J1 AMP P.C.B. HEADER P/N 640445-5
PIN 1) AC LINE
PIN 2) N/C
PIN 3) AC NEUTRAL
PIN 4) N/C
PIN 5) AC GROUND
MATING CONNECTOR AMP P/N
HOUSING 640250-5
CONTACT 770476-1
SIGNALS: J2
AMP P.C.B. HEADER P/N 640456-4
MATING CONNECTOR P/N 640440-4
PIN 1) POWER FAIL
PIN 2) -SENSE
PIN 3) +SENSE
PIN 4) COMMON
OUTPUT: J3 AMP P.C.B HEADER P/N 1-640445-3
PIN 1) -V4OUT
PIN 2-4) +V1OUT
PINS 5-9) COMMON
PIN 10,11) +V2 OUT
PIN 12) +V3OUT
PIN 13) -V3RTN
MATING CONNECTOR AMP P/N
HOUSING 1-640250-3
CONTACT 770476-1
OPTIONAL COVER P/N 08-30466-2125
WEIGHT: 1.25 LBS [ .56 KG]
GPFC125/GPFM125 MECHANICAL SPECIFICATIONS
Notes:
A. Continuous rating for unrestricted convection cooling.
B. Peak rating or continuous rating with 150 LFM air cooling.
C. Output 3 is isolated. Can be connected as + or - output.
Commercial Medical Voltage Output Voltage Output Qutput Voltage OVP To t al Ripple/
Model Model Output No. Current (A) Current (B) Adjustment Regulation Noise
GPFC125A GPFM125A 1 +5 V 9 A 16 A ±5% 6.2 ±0.6 V 1% 1%
2 +12 V 4 A 7 A ±5% -- 1% 1%
312 V (C)2.5 A4 A -- -- 1%1%
4-12 V0.3 A1 A -- -- 1%1%
GPFC125B GPFM125B 1 +5 V 9 A 16 A ±5% 6.2 ±0.6 V 1% 1%
2 +12 V 4 A 7 A ±5% -- 1% 1%
312 V (C)2.5 A4 A -- -- 1%1%
4-5 V0.3 A1 A-- --1%1%
GPFC125C GPFM125C 1 +5 V 9 A 16 A ±5% 6.2 ±0.6 V 1% 1%
2 +12 V 4 A 7 A ±5% -- 1% 1%
315 V (C)2.5 A4 A -- -- 1%1%
4-15 V0.3 A1 A -- -- 1%1%
GPFC125D GPFM125D 1 +5 V 9 A 16 A ±5% 6.2 ±0.6 V 1% 1%
2 +24 V 3 A 4.5 A ±5% -- 1% 1%
312 V (C)2.5 A4 A -- -- 1%1%
4-12 V0.3 A1 A -- -- 1%1%
GPFC125E GPFM125E 1 +5 V 9 A 16 A ±5% 6.2 ±0.6 V 1% 1%
2 +24 V 3 A 4.5 A ±5% -- 1% 1%
315 V (C)2.5 A4 A -- -- 1%1%
4-15 V0.3 A1 A -- -- 1%1%
GPFC125F GPFM125F 1 +5 V 9 A 16 A ±5% 6.2 ±0.6 V 1% 1%
2 +15 V 3.5 A 6 A ±5% -- 1% 1%
315 V (C)2.5 A4 A -- -- 1%1%
4 - 5 V 0.3 A 1 A -- -- 1% 1%
GPFC125G GPFM125G 1+5 V
9 A
16 A ±5% 6.2 ±0.6 V 1% 1%
2 +3.3 V 7 A 10 A ±5% 4.2 ±0.6 V 1% 2%
312 V (C)2.5 A4 A -- -- 1%1%
4-12 V0.3 A1 A -- -- 1%1%
GPFC125H GPFM125H 1 +3.3 V 9 A 16 A ±5% 4.2 ±0.6 V 1% 2%
2 +5 V 4 A 7 A ±5% 6.2 ±0.6 V 1% 1%
312 V (C)2.5 A4 A -- -- 1%1%
4-12 V0.3 A1 A -- -- 1%1%

GPFC125DG

Mfr. #:
Manufacturer:
Description:
Switching Power Supplies 125W +5/+24/+12/-12