PHOENIX CONTACT page 4 of 10
11
11
AC input:
Input voltage 85 - 264 V AC/90 - 250 V DC
Frequency 45 - 65 Hz
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible)
(25 - 14 AWG)
Internal fuse 6.3 AT
Recommended fuse
10 A or 16 A c.b./Characteristic B
22
22
DC output:
Output voltage 24 V DC (default), can be set from
22.5 - 28.5 V DC using a potentiometer
5
(0.2 mm
2
to 2.5 mm
2
solid) (0.2 mm
2
to 2.5 mm
2
flexible)
(25 - 14 AWG)
The device is idling-proof and short-circuit-proof.
33
33
DC OK output active
44
44
DC OK output electrically isolated
55
55
Potentiometer (covered) 22.5 - 28.5 V DC
66
66
DC OK LED
77
77
Universal DIN rail adapter UTA 107
5. Safety Notes and Warning
Instructions
To ensure safe operation of the device, please read
these instructions carefully.
Installation, startup, and maintenance must only be
carried out by qualified personnel. The relevant
country-specific safety rules and regulations for the
prevention of accidents must also be observed.
Caution: Never carry out work when the
power is turned on, this is highly
dangerous. The circuits inside the device
must not be accessed during operation.
O
u
tp
u
t D
C
2
4
V
1
0
A
+ +
– –
D
C
O
K
13 14
D
C
O
K
A
d
ju
st
2
2
.5-2
8.5V
Inp
u
t
A
C
1
00-24
0
V
LN
5
QUINT POWER
APPROVALS
Read installation instructions
before connecting to mains
- 25 … + 60 °C
- 13 … + 140 °F
EN 60950
EN 60204
EN 61558-2-17
B
EN 61000-6-2
EN 50081-1
F
www.interface.phoenixcontact.com
U
INDUSTRIAL
CONTROL
EQUIPMENT
1XD4
LISTED
–25
DC OK
QUINT-PS-100-240AC/24DC/10/EX
Order-No.: 29 38 86 6
Inp.: 100-240VAC/50-60Hz/2.8-1.2A
Operational Voltage 85-264VAC
Inp.: 90-350VDC
Outp.:24VDC/10A
xxx
REV xx
xxx xxx
II 3G EEx nAC T4
TÜV03 ATEX ...
xxx
13 14
DC
OK
+ + – –
13 14
DC
OK
+ + – –
Output DC 2
+ +
–
DC
O
K
13 14
Figure 04
7
2
1
3
4
5
6
1-Phase Power Supply, Primary Switch Mode for Use in Potentially Explosive Areas –
QUINT 24 V DC/10A/EX
4. Device View, Connections, and Control Elements
When installing and operating electrical equipment,
the applicable national safety standards and the
general technical regulations (e.g., EN 60 079-14 VDE
0165 Part 1) must be observed. It is particularly
important to ensure that:
– The mains have been connected correctly and
protection is provided against electric shock.
– The device can be switched off outside the power
supply according to EN 60950 regulations (e.g., by
the line protection on the primary side).
– The protective conductor is connected.
– All supply lines and outgoing cables have sufficient
fuse protection and are the correct size for the
current flow.
– Installation is carried out following the instructions
provided.
– The specified mechanical or thermal limits are not
exceeded during operation.
– At least IP 54 protection according to EN60529 is
achieved after installation.
– If dust is present, the device must be installed in
suitable housing.
– Only devices, which are suitable for operation in
potentially explosive areas of zone 2 and are suited
to the conditions at the installation location can be
connected to supply and signal circuits in zone 2.
– When using a DC input voltage of more than 120 V,
a suitable fuse must be fitted.