2692076

https://www.phoenixcontact.com/us/products/2692076
09/03/2014Page1/6
I/O module-ILB S3 AI4 AO2-2TX-2692076
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Inline Block IO Analog I/O module, Sercos III, inputs: 0-20 mA, 4-20 mA, ±20 mA, 0-5 V, ±5 V, 0-10 V, ±10
V, Pt100, Pt1000, Ni1000..., outputs: 0-5 V, ±5 V, 0-10 V, ±10 V, 0-20mA, ±20 mA, 4-20mA, 2-, 3-, 4-wire
connection
Product description
The multifunctional, analog Inline Block I/O modules can be used universally. The four inputs either offer the difference measured between analog
current / voltage signals or the option of connecting resistance thermometers (RTDs). Furthermore, the current or voltage actuators can be connected at
the two outputs. In addition, all channels are equipped with shield connections as a standard and are provided with the 2, 3 or 4-conductor system. The
analog signals are made available with a resolution of 16 bits.
The plugs can be labeled using hinged labeling fields. The fields have insert cards that can be labeled individually to suit the application. Additionally,
there is the proven ZBFM-6... Zack marker strip for labeling the terminal points. 
Product Features
Short-circuit-proof outputs
2 shielded analog signal outputs with 4 voltage and 3 current ranges
Sensor supply with channel-specific integrated short-circuit and overload protection
Adjustable filter times
4 voltage measuring ranges and 3 current measuring ranges
4 shielded analog differential signal inputs or 4 universal RTD inputs
Connection of actuators in 2-wire technology
Connection of sensors in 2, 3, and 4-wire technology
Key commercial data
Packing unit 1 pc
Custom tariff number 85176200
Country of origin Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
https://www.phoenixcontact.com/us/products/2692076
09/03/2014Page2/6
I/O module-ILB S3 AI4 AO2-2TX-2692076
Technical data
Dimensions
Width 156 mm
Height 136.8 mm
Depth 57 mm
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 10 % ... 85 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 108 kPa (up to 3500 m above mean sea level)
Air pressure (storage/transport) 70 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection IP20
General
Weight 465 g
Mounting type DIN rail
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Test section Sercos III/logic area 500 V AC 50 Hz 1 min
Sercos III/analog I/O 500 V AC 50 Hz 1 min
Sercos III/communications power 500 V AC 50 Hz 1 min
Sercos III/initiator supply 500 V AC 50 Hz 1 min
Sercos III/functional earth ground 500 V AC 50 Hz 1 min
Logic/analog I/O 500 V AC 50 Hz 1 min
Logic area/initiator supply 500 V AC 50 Hz 1 min
Logic area/functional earth ground 500 V AC 50 Hz 1 min
Analog I/O/communications power 500 V AC 50 Hz 1 min
Analog I/O/initiator supply 500 V AC 50 Hz 1 min
Functional earth ground/analog I/O (isolating distance) 500 V AC 50 Hz 1
min
Functional earth ground/communications power 500 V AC 50 Hz 1 min
Functional earth ground/initiator supply 500 V AC 50 Hz 1 min
Mechanical tests Vibration resistance in acc. with EN60068-2-6/IEC60068-2-6 5g
Shock in acc. with EN60068-2-27/IEC60068-2-27 30g
Interfaces
Fieldbus system Sercos
Designation Inline local bus
Connection method RJ45 socket, shielded
Transmission speed 100 MBit/s
https://www.phoenixcontact.com/us/products/2692076
09/03/2014Page3/6
I/O module-ILB S3 AI4 AO2-2TX-2692076
Technical data
Interfaces
Transmission physics Copper
Inline potentials
Communications power U
L
24 V DC
Power supply at U
L
max. 8 A
Current consumption from U
L
max. 220 mA (AO-I nominal load)
Segment supply voltage U
S
24 V DC
Power supply at U
S
max. 8 A
Current consumption from U
S
max. 220 mA (Maximum full load)
Axioline potentials
Analog inputs
Number of inputs max. 4 (Differential inputs, voltage or current can be chosen separately)
Connection method Spring-cage connection
2, 3, 4-wire (shielded)
Input name Analog inputs
A/D conversion time typ. 180 µs
Resolution A/D 16 bit
Limit frequency (3 dB) 120 Hz (default for 4.5 ms filter)
450 Hz (for 1.1 ms filter)
Data formats IB IL, S7-compatible
Measured value resolution 16 bits (15 bits + sign bit)
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input typ. 107 Ω
Voltage input signal 0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input typ. 276 kΩ
Number of inputs 4 (differential inputs, voltage)
Type of protection Overload protection, short-circuit protection of sensor supply
Open circuit response Goes to 0V
Voltage input signal 0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V

2692076