https://www.phoenixcontact.com/us/produkte/2985864
18.03.2013Page2/7
Safety module-IB IL 24 PSDOR 4-PAC-2985864
Technical data
Interface
Transmission speed 500 kbaud/2 Mbaud, can be selected
Transmission speed 500 kBit/ / 2 MBit/s
Digital outputs
Output name Relay output
Connection method Spring-cage connection
Connection method 2, 3, 4-wire
Number of outputs 4 (Safety relays)
Output voltage
24 V DC (U
S
- 1 V)
Nominal output voltage 24 V DC (Inline connector)
Output current max. 4 A (Inline connector, pro contact, observe derating)
Output current max. 6 A (COMBICON connector, pro contact, observe derating)
Maximum output current per channel 4 A
Power supply for module electronics
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC
Communications power U
L
7.5 V (via voltage jumper)
Current consumption max. 360 mA (from the local bus)
General data
Width 73.2 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
Weight 310 g
Note on weight specifications with male connectors
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Permissible humidity (storage/transport)
10 % ... 85 % (Take suitable measures against increased air humidity
within the permitted temperature range.)
Air pressure (operation) 80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection IP20
Protection class I, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC
50 Hz 1 min