Description
• Fast-acting glass tube fuse
•
1
/4" x 1" (6.3 x 25.4mm) physical size
• Glass tube, nickel-plated brass endcap construction
• For instruments, electronic and small appliance circuits
• UL Listed product meets standard 248-14
Electrical Characteristics
Rated Current % of Amp Rating Opening Time
1
/10 - 30A
110% 4 hours. min.
135% 60 minutes max.
1
/10 - 2A
200% 5 seconds max.
2.5 - 30A
200% 2 minutes max.
* Typical DC Cold Resistance (Measured at <10% of rated current).
** Component Recognized rating 125V & 250V.
*** Component Recognized rating 125V.
Specifications
Part Number Voltage Interrupting
Rating (amps)
Typical DC Cold Resistance (Ω)* Agency Approvals
(Amps) Rating Vac 250Vac 125Vac 32Vac Lower Upper cULus cURus
AGX-
1
/
10 250 35 10,000 - N/A N/A X -
AGX-
1
/
8 250 35 10,000 - 7.610 10.293 X -
AGX-
3
/16 250 35 10,000 - 3.086 4.176 X -
AGX-
2
/
10 250 35 10,000 - 2.918 3.948 X -
AGX-
1
/
4 250 35 10,000 - 1.010 1.366 X -
AGX-
3
/10 250 35 10,000 - 0.789 1.067 X -
AGX-
3
/8 250 35 10,000 - 0.547 0.740 X -
AGX-
4
/
10 250 35 10,000 - 0.514 0.568 X -
AGX-
1
/2 250 35 10,000 - 0.318 0.431 X -
AGX-
3
/4 250 35 10,000 - 0.158 0.215 X -
AGX-1 250 35 10,000 - 0.111 0.150 X -
AGX-1-
1
/4 250 100 10,000 - 0.080 0.109 X -
AGX-1-
1
/
2 250 100 10,000 - 0.064 0.086 X -
AGX-2 250 100 10,000 - 0.041 0.055 X -
AGX-2-
1
/2 250 100 10,000 - 0.031 0.043 X -
AGX-3 250 100 10,000 - 0.027 0.036 X -
AGX-4 250 200 10,000 - 0.021 0.028 X -
AGX-5 250 200 10,000 - 0.014 0.019 X -
AGX-6 250 200 10,000 - 0.011 0.015 X -
AGX-7 250 200 10,000 - 0.009 0.015 X -
AGX-8 250 200 10,000 1000 0.008 0.011 X -
AGX-10 250 200 10,000 1000 0.006 0.008 X -
AGX-15** 250 200 200 1000 0.004 0.005 - X
AGX-20** 250 200 200 1000 0.003 0.003 - X
AGX-25*** 125 - 100 1000 0.002 0.003 - X
AGX-30*** 125 - 100 1000 0.002 0.002 - X
1
/4" x 1" Fast-Acting, Glass Tube Fuses
AGX Series
25.4±0.8
1.000±0.31
6.35±0.1
0.250±0.004
1011 BU-SB11901 Page 1 of 2 Data Sheet 2041
Agency Information
• cULus: AGX 0-10A (Guide JDYX, File E 19180 and Guide JDYX7, File
E19180)
• UL Recognized Card: AGX 15-30A (Guide JDYX2, File E19180)
• CSA Component Acceptance Card : AGX 15-30A (Class No. 1422-01,
File 53787)
Ordering
• Insert packaging code prefix before part number, e.g., BK/AGX-1
Dimensions - mm (in)