Attachment plug with replaceable surge protection for coaxial signal interfaces, transmission capacity ≤200 W.
Connection: UHF female/female.
Key commercial data
Packing unit 1 pc
GTIN
Weight per Piece (excluding packing) 79.89 GRM
Custom tariff number 85363010
Country of origin Germany
Technical data
Dimensions
Height 40 mm
Width 60.5 mm
Length 18.1 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... -90 °C
Degree of protection IP20
General
Housing material Nickel-plated brass
Color silver
Mounting type Connection-specific intermediate plugging
Type Attachment plug
Direction of action Line-Shield/Earth Ground
https://www.phoenixcontact.com/us/products/2782135
09/09/2014Page2/5
Surge protection device-RF-TRAB-2782135
Technical data
Protective circuit
IEC test classification C2
C3
D1
Maximum continuous operating voltage U
C
130 V AC
Maximum continuous voltage U
C
(wire-ground)
130 V AC
Maximum continuous voltage U
C
(wire-shield)
130 V AC
Nominal current I
N
10 A (25 °C)
Operating effective current I
C
at U
C
≤ 1 µA
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
(8/20) µs (Core-Earth)
10 kA
Nominal discharge current I
n
(8/20) µs (Core-Shield)
10 kA
Total surge current (8/20) µs 10 kA
Output voltage limitation at 1 kV/µs (Core-Earth) spike ≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Shield) spike ≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Earth) static ≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Shield) static ≤ 600 V
Voltage protection level U
P
(Core-Earth)
≤ 600 V
Voltage protection level U
P
(Core-Shield)
≤ 600 V
Response time tA (Core-Earth) ≤ 100 ns
Response time tA (Core-GND) ≤ 100 ns
Input attenuation aE, asym. 0.3 dB (≤ 250 MHz)
Cut-off frequency fg (3 dB), asym. (shield) in 50 Ohm system typ. 950 MHz
Standing wave ratio SWR in a 50 Ω system ≤ 1.2 (≤ 80 MHz)
Permissible HF power P
max
at VSWR = xx (50 ohm system)
300 W (VSWR = 1.1)
80 W (VSWR = ∞)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C2 - 10 kV / 5 kA
D1 - 2,5 kA
Connection data
Connection method UHF connector
Connection type IN UHF connector, female
Connection type OUT UHF connector, female
Connection, equipotential bonding
Connection method Screw terminal block
Standards and Regulations
Standards/regulations IEC 61643-21
https://www.phoenixcontact.com/us/products/2782135
09/09/2014Page3/5
Surge protection device-RF-TRAB-2782135
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130807
eCl@ss 7.0 27130807
eCl@ss 8.0 27130807
ETIM
ETIM 2.0 EC000943
ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 5.0 EC000943
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
Approvals
GOST
Ex Approvals
Approvals submitted
Approval details

2782135

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
RF Adapters - In Series RF-TRAB ADPT UHF CON 200W
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet