Amp meter changeover switch, Connection method:Screw connection, Number of positions:2, Function:
0‑1‑2‑3, Switching zones:5, Switching program number:S0038, Rated continuous current:20 A,
Voltage:690 V
Why buy this product
The compact rotary switch is designed for use in energy technology applications with the available switching programs
The use of high-quality materials results in a long mechanical and electrical service life
Comprehensive approvals ensure international use
High level of safety thanks to non-conductive plastic parts
The terminal points are designed in such a way that shock protection according to BGV A2 is ensured
The rotary switch is free from cadmium and compliant with the RoHS directive
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356771498
Technical data
General
Number of connections 20
Color silver/black
Rotary switch function 0‑1‑2‑3
Switching program number S0038
Switching angle 90 °
Rated continuous current 20 A
Maximum load current 20 A
Rated surge voltage 6 kV
https://www.phoenixcontact.com/pi/products/3069703
05/02/2017Page2/5
Amp meter changeover switch-RS20-US-
S0038-0504-014H-001-3069703
Technical data
General
Rated insulation voltage
690 V (Valid for networks with grounded neutral point, overvoltage
category III, degree of pollution 3)
Rated operating current according to AC-15 (switching of solenoid
drives, contactors, valves, pulling electromagnets)
5 A (220 - 240 V)
4 A (380 - 440 V)
Rated operating current according to AC-21A (switching of ohmic loads
including small overloads)
20 A
Rated operating current according to AC-22A (switching of mixed ohmic
and inductive loads, including small overloads)
20 A (220 - 500 V)
20 A (660 - 690 V)
Switching power according to AC-3 (squirrel-cage motors: direct starting,
switching off motors during operation, star-delta startup (CH16B))
3 kW (220 - 240 V; 3-phase, 3-pos.)
5.5 kW (380 - 440 V; 3-phase, 3-pos.)
5.5 kW (500 V; 3-phase, 3-pos.)
5.5 kW (660 - 690 V; 3-phase, 3-pos.)
0.6 kW (110 - 120 V; 1-phase, 2-pos.)
2.2 kW (220 - 240 V; 1-phase, 2-pos.)
3 kW (380 - 440 V; 1-phase, 2-pos.)
Switching power according to AC-4 (squirrel-cage motors: starting,
reversing, plugging, inching)
0.55 kW (220 - 240 V; 3-phase, 3-pos.)
1.5 kW (380 - 440 V; 3-phase, 3-pos.)
1.5 kW (500 V; 3-phase, 3-pos.)
1.5 kW (660 - 690 V; 3-phase, 3-pos.)
0.3 kW (110 - 120 V; 1-phase, 2-pos.)
0.75 kW (220 - 240 V; 1-phase, 2-pos.)
1.5 kW (380 - 440 V; 1-phase, 2-pos.)
Switching power according to AC-23A (frequent switching of motors or
other highly inductive loads)
3.7 kW (220 - 240 V; 3-phase, 3-pos.)
7.5 kW (380 - 440 V; 3-phase, 3-pos.)
7.5 kW (500 V; 3-phase, 3-pos.)
7.5 kW (660 - 690 V; 3-phase, 3-pos.)
0.75 kW (110 - 120 V; 1-phase, 2-pos.)
2.5 kW (220 - 240 V; 1-phase, 2-pos.)
3.7 kW (380 - 440 V; 1-phase, 2-pos.)
Breaking capacity 150 A (220 - 240 V)
150 A (380 - 440 V)
80 A (660 - 690 V)
Maximum power dissipation for nominal condition 1.8 W
Ambient temperature (operation) -35 °C ... 55 °C (Open, at 100% load, with peaks up to 60°C)
IP immunity to short-circuiting with maximum backup fuse 25 A (gL/gG characteristics)
Rated short-time current resistance 140 A (1 s current)
https://www.phoenixcontact.com/pi/products/3069703
05/02/2017Page3/5
Amp meter changeover switch-RS20-US-
S0038-0504-014H-001-3069703
Technical data
Dimensions
Width 48 mm
Length 100.5 mm
Height 48 mm
Hole diameter 7 mm
Height 29 mm
Installation depth 71.5 mm
Ambient conditions
Ambient temperature (operation) -35 °C ... 55 °C (Open, at 100% load, with peaks up to 60°C)
Connection data
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 14
Conductor cross section flexible min. 0.75 mm²
Conductor cross section flexible max. 2.5 mm²
Min. AWG conductor cross section, flexible 18
Max. AWG conductor cross section, flexible 14
Conductor cross section / stranded with ferrule without plastic sleeve
min.
2.5 mm²
Conductor cross section / stranded with ferrule without plastic sleeve
max.
2.5 mm²
Conductor cross section / stranded with ferrule with plastic sleeve min. 1.5 mm²
Conductor cross section / stranded, with ferrule with plastic sleeve max. 1.5 mm²
2 conductors with same cross section, solid min. 0.5 mm²
2 conductors with same cross section, solid max. 2.5 mm²
Two conductors with the same cross section, AWG solid min. 20
Two conductors with the same cross section, AWG solid max. 14
2 conductors with same cross section, stranded min. 0.75 mm²
2 conductors with same cross section, stranded max. 2.5 mm²
Two conductors with the same cross section, AWG stranded, min. 18
Two conductors with the same cross section, AWG stranded, max. 14
2 conductors with the same cross section/stranded, with ferrule and
without plastic sleeve, minimum
2.5 mm²
2 conductors with the same cross section/stranded, with ferrule and
without plastic sleeve, maximum
2.5 mm²
2 conductors with the same cross section/stranded, with ferrule and
plastic sleeve, minimum
1.5 mm²
2 conductors with the same cross section/stranded, with ferrule and
plastic sleeve, maximum
1.5 mm²