https://www.phoenixcontact.com/pi/products/2909530
08/20/2018Page2/5
Relay Module-PLC-RPT-230UC/21/EX-2909530
Technical data
Coil side
Typical response time 7 ms
Typical release time 15 ms
Protective circuit Bridge rectifier Bridge rectifier
Operating voltage display Yellow LED
Power dissipation for nominal condition 0.74 W
Contact side
Contact type 1 PDT
Type of switch contact Single contact
Contact material AgSnO
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed for
voltages larger than 250 V (L1, L2, L3) between identical terminal blocks
in adjacent modules. Potential bridging is then carried out with FBST 8-
PLC... or ...FBST 500...)
Minimum switching voltage 5 V (at 100 mA)
Min. switching current 10 mA (at 12 V)
Maximum inrush current 10 A (4 s)
Limiting continuous current 6 A
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
20 W (at 48 V DC)
18 W (at 60 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity in acc. with DIN VDE 0660/IEC 60947 2 A (at 24 V, DC13)
0.2 A (at 110 V, DC13)
0.1 A (at 220 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 230 V, AC15)
General
Test voltage relay winding/relay contact 4 kV AC (50 Hz, 1 min.)
Operating mode 100% operating factor
Degree of protection IP20 (Relay base)
Mechanical service life
2x 10
7
cycles
ATEX II 3G Ex ec nC IIC T4 Gc
EU-type examination certificate IBExU16ATEXB015 X
IECEx Ex ec nC IIC T4 Gc
IECEx certificate IECEx IBE 16.0029X
UL, USA Class I, Zone 2, AEx nA nC IIC T6
UL, USA/Canada Class I, Div. 2, Groups A, B, C, D
UL, Canada Class I, Zone 2, Ex nA nC IIC Gc T6 X