600APH12P

1 PLC
0 PLC
2 PLC
3 PLC
4 PLC
DIMENSIONS:
TOLERANCES UNLESS
OTHERWISE SPECIFIED:
ANGLES
WEIGHT
APPLICATION SPEC
PRODUCT SPEC
OF
MATERIAL FINISH
DWN
CHK
APVD
NAME
SIZE CAGE CODE DRAWING NO
SCALE SHEET REV
LOC DIST
RELEASED FOR PUBLICATION
C
COPYRIGHT
ALL RIGHTS RESERVED.
THIS DRAWING IS UNPUBLISHED.
REVISIONS
P LTR
DATE
DWN APVDDESCRIPTION
1469-35 (3/11)
A4
RESTRICTED TO
THIS DRAWING IS A CONTROLLED DOCUMENT.
TE Connectivity
A
REVISED PER ECR-14-007823
02JUN2014
RS
EC
B
ECO-15-015144: ADD UL.
03NOV2015
EC
EC
Customer Drawing
8-1609148-9
RS
13DEC2013
EC
13DEC2013
EC
13DEC2013
1:1
1 1
B
-
-
-
- -
mm
2
1
0.5
0.2
0.0001
-
- -
600APH12P
3-PHASE DELTA FILTER
-
20
20
00779
BY -
12
260
235
300
40
25
10.5
25
40
37
150
210
45
60
8
*12
30
140 100
MHz 0.01 0.05 0.15 0.5 1.0 3.0 5.0 10 30
CM 11 25 68 88 72 70 60 43 24
DM 31 43 71 73 62 50 45 38 27
LINE
LOAD
* DO NOT LOOSEN INNER GROUND NUTS.
TORQUE OUTER GROUND NUTS TO:
25-30 NM [220-260 IN-LB]
SAFETY ORGANIZATIONS
THIS FILTER HAS BEEN FORMALLY RECOGNIZED, CERTIFIED OR APPROVED
BY THE LISTED AGENCY. THEREFORE, ALL TEST/REQUIREMENTS SPECIFIED
IN THE LATEST REVISION OF THE FOLLOWING AGENCY STANDARDS
HAVE BEEN MET:
UL
OPERATING SPECIFICATIONS
LINE CURRENT/VOLTAGE: 600 A, 690 VAC
LINE FREQUENCY: 50-60 Hz
NOMINAL LEAKAGE CURRENT: 10 mA
MAXIMUM LEAKAGE CURRENT: 330mA @ 400V, 50HZ
OPERATING AMBIENT TEMPERATURE RANGE
@ RATED CURRENT, I : -10$C TO +50$C
IN AN AMBIENT, T , HIGHER THAN 50°C,
THE MAXIMUM OPERATING 100 - T
CURRENT, I , IS AS FOLLOWS: I = I
50
RO
Q
RELIABILITY SPECIFICATIONS
STORAGE TEMPERATURE: -40$C TO +85$C
HUMIDITY: 21 DAYS @ 40$C AND 95% RH
TEST SPECIFICATIONS
INDUCTANCE, NOMINAL: 88.7 µH
CAPACITANCE @ 1 kHz, 0.25 VAC MAX., 25$C #1$C:
LINE TO GROUND, NOMINAL: 2.62 µF
LINE TO LINE, NOMINAL: 11.9 µF
DISCHARGE RESISTOR
L/G AND L/L I.R. 666k^/666k^
IR (NO DISCHARGE RESISTOR) 20°C, 50% RH AND 100VDC, MIN: 6000M^
RECOMMENDED RECEIVING INSPECTION HIPOT
LINE TO GROUND FOR 1 MINUTE: 2640 VDC
LINE TO LINE FOR 1 MINUTE: 2520 VDC
FILTER APPROVAL:
THE BEST WAY TO SELECT AND QUALIFY
A FILTER IS FOR YOUR ENGINEERING TO
TEST THE UNIT IN YOUR EQUIPMENT.
TYPICAL INSERTION LOSS
COMMON MODE 50/50 ^; DIFFERENTIAL MODE 100/100 ^

600APH12P

Mfr. #:
Manufacturer:
TE Connectivity
Description:
LINE FILTER 690VAC 600A CHASS
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet