VOLTAGE REGULATION
Voltage Regulation Description Includes automatic voltage regulation to correct brownouts and overvoltages back to usable levels
Overvoltage Correction Overvoltages are automatically reduced by 10%
Brownout Correction Brownouts are automatically boosted by 10% and 20%
USER INTERFACE, ALERTS & CONTROLS
Front Panel LEDs Set of 6 LEDs offer continuous status information on load percentage (6 levels reported) and battery charge level (7
levels reported). See manual for sequences.
Switches 3 position on/off/remote switch enables simple on/off power control plus "auto/remote" setting that enables distant
on/off control of the inverter system when used in conjunction with optional <a class="productLink"
href="//www.tripplite.com/Remote-Control-Module-Tripp-Lite-PowerVerter-Inverters-Inverter-
Chargers~APSRM4">APSRM4</a> accessory when used in inverter mode. In AC uninterrupt
PHYSICAL
Shipping Dimensions (hwd / in.) 20.080 x 18.430 x 22.520
Shipping Dimensions (hwd / cm) 51.00 x 46.81 x 57.20
Shipping Weight (lbs.) 87.0000
Shipping Weight (kg) 39.46
Unit Dimensions (hwd / in.) 10.08 x 8.90 x 12.40
Unit Dimensions (hwd / cm) 25.60 x22.606 x 31.496
Unit Weight (lbs.) 64.8
Unit Weight (kg) 29.39
Cooling Method Fan
Material of Construction Metal
ENVIRONMENTAL
Relative Humidity 0-95% non-condensing
Operating Temperature 32-104 Fahrenheit / 0-40 Celcius
LINE / BATTERY TRANSFER
Transfer Time (Line Power to
Battery Mode)
Dip-switch selectable 20 millisecond (full cycle) / 10 millisecond (half-cycle) transfer times which are compatible with
many computers, servers and networking equipment - verify transfer time compatibility of loads for UPS applications
Low Voltage Transfer to Battery
Power
In 230V AC "auto" mode, inverter/charger switches to battery mode as line voltage drops to 170V AC (user
adjustable to 180V).
High Voltage Transfer to Battery
Power
In 230V AC "auto" mode, inverter/charger switches to battery mode as line voltage increases to 260V (user
adjustable to 270 - see manual).
SPECIAL FEATURES
TVSS Grounding Main grounding lug connects inverter/charger to earth or vehicle chassis ground
CERTIFICATIONS