4
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Table 3. Part numbers sizes 1 to 4
Size Rated
current
(Amps)
Rated
voltage
(V a.c.)
gG/gL dual indicator Pack
quantity
Voltage conducting
metal gripping lugs
Insulated metal
gripping lugs
1 50 500 50NHG1B 50NHG1BI* 3
1 63 500 63NHG1B 63NHG1BI* 3
1 80 500 80NHG1B 80NHG1BI* 3
1 100 500 100NHG1B 100NHG1BI* 3
1 125 500 125NHG1B 125NHG1BI* 3
1 160 500 160NHG1B 160NHG1BI* 3
1 200 500 200NHG1B 200NHG1BI 3
1 224 500 224NHG1B 224NHG1BI 3
1 250 500 250NHG1B 250NHG1BI 3
1 315 440 315NHG1B 315NHG1BI* 3
1 355 440 355NHG1B 355NHG1BI* 3
02 35 500 35NHG02B 35NHG02BI 3
02 40 500 40NHG02B 40NHG02BI 3
02 50 500 50NHG02B 50NHG02BI 3
02 63 500 63NHG02B 63NHG02BI 3
02 80 500 80NHG02B 80NHG02BI 3
02 100 500 100NHG02B 100NHG02BI 3
02 125 500 125NHG02B 125NHG02BI 3
02 160 500 160NHG02B 160NHG02BI 3
02 200 500 200NHG02B 200NHG02BI 3
02 224 500 224NHG02B 224NHG02BI 3
02 250 500 250NHG02B 250NHG02BI 3
2 250 500 250NHG2B 250NHG2BI* 3
2 300 500 300NHG2B 300NHG2BI* 3
2 315 500 315NHG2B 315NHG2BI 3
2 355 500 355NHG2B 355NHG2BI 3
2 400 500 400NHG2B 400NHG2BI 3
2 425 500 425NHG2B 425NHG2BI* 3
2 450 500 450NHG2B 450NHG2BI* 3
2 500 440 500NHG2B 500NHG2BI* 3
03 250 500 250NHG03B 250NHG03BI 3
03 315 500 315NHG03B 315NHG03BI 3
03 355 500 355NHG03B 355NHG03BI 3
03 400 500 400NHG03B 400NHG03BI 3
3 315 500 315NHG3B - 3
3 355 500 355NHG3B - 3
3 400 500 400NHG3B - 3
3 425 500 425NHG3B - 3
3 500 500 500NHG3B - 3
3 630 500 630NHG3B - 3
3 800 440 800NHG3B - 3
4** 500 500 500NHG4G - 1
4** 630 500 630NHG4G - 1
4** 800 500 800NHG4G - 1
4** 1000 500 1000NHG4G - 1
4** 1250 500 1250NHG4G - 1
* Available upon request
** Single indicator and slotted end tags
5
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 000
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)
Technical data - NH size 000
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
2NHG000B 2NHG000BI 000 2 500 3.5 6 3.9 0.13
4NHG000B 4NHG000BI 4 6 12 1.8
6NHG000B 6NHG000BI 6 14 21 2
10NHG000B 10NHG000BI 10 58 290 1.5
16NHG000B 16NHG000BI 16 234 1200 2.3
20NHG000B 20NHG000BI 20 490 2500 2.2
25NHG000B 25NHG000BI 25 920 4600 3.1
32NHG000B 32NHG000BI 32 1800 9000 3.4
35NHG000B 35NHG000BI 35 2400 11,800 3.7
40NHG000B 40NHG000BI 40 3300 16,500 4
50NHG000B 50NHG000BI 50 5900 29,500 4.9
63NHG000B 63NHG000BI 63 6300 24,900 4.6
80NHG000B 80NHG000BI 80 9800 38,900 6.3
100NHG000B 100NHG000BI 100 18,100 72,300 7.4
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements
6
Technical Data 10164
Effective September 2015
Bussmann series
500 Volts gG/gL NH Fuse links
EATON www.eaton.com
Time-current curves - NH Size 00
Time in seconds (s)
Time in seconds (s)
Current in Amps (A)
Current in Amps (A)
Technical data - NH size 00
Part numbers
with metal
gripping lugs
Part numbers
with insulated
metal gripping
lugs
Fuse link
size
Rated
current
(Amps)
Rated
voltage
(V a.c.)
I
2
t (Amps
2
Seconds)
Watts loss
Net weight
per fuse
(kg)
Minimum
pre-arcing
*I
1
120kA
at 500 V a.c.
50NHG00B 50NHG00BI** 00 50 500 5800 21,500 5 0.19
63NHG00B 63NHG00BI** 63 5800 25,000 5
80NHG00B 80NHG00BI** 80 11,000 35,000 7
100NHG00B 100NHG00BI** 100 19,000 60,000 7.5
125NHG00B 125NHG00BI 125 25,000 125,000 10
160NHG00B 160NHG00BI 160 64,000 310,000 10
*I
1
is the maximum breaking capacity test at rated voltage according to IEC 60269 requirements