MJN1CF-AC240

General Purpose Relay MJN 317
General Purpose Relay
MJN
Relay with Plug-in Termination, available
in SPDT, DPDT or 3PDT models
• Rugged power driver offers superior 3/16” through-air
and 3/8 over-surface spacing
• Interlocked frame and contact block prevent contact
misalignment during plug-in
• Available with dust covers, indicator lamps and
push-to-operate buttons
UL and CSA recognition as motor controllers up to 600 VAC
• Recognized for 1/2 hp motor control applications at 240/
480/600 VAC (1/3 hp at 120 VAC)
R C
Ordering Information
To Order: Select part number and add the desired coil voltage rating (e.g. MJN1C-AC24).
Note: All part numbers marked with an “*” are non-standard parts. Contact an Omron representative for additional information.
Item Model
Type Terminal Contact form 10A Version,
flange
mounting
20 A Version,
flange
mounting
30A Version,
flange
mounting
10 A Relay only
Standard Plug-in SPDT MJN1CF --- MJN1Z-E-RP MJN1C
DPDT MJN2CF MJN2CE --- MJN2C
3PDT MJN3CF --- --- MJN3C
LED indicator Plug-in SPDT MJN1CF-N* --- --- MJN1C-N
DPDT MJN2CF-N* --- --- MJN2C-N
3PDT MJN3CF-N* --- --- MJN3C-N
Push-to-operate
button
Plug-in SPDT MJN1CF-I* --- --- MJN1C-I
DPDT MJN2CF-I* --- --- MJN2C-I
3PDT MJN3CF-I* --- --- MJN3C-I
Push-to-operate
button & LED indi-
cator
Plug-in SPDT MJN1CF-IN* --- --- MJN1C-IN
DPDT MJN2CF-IN* --- --- MJN2C-IN
3PDT MJN3CF-IN* --- --- MJN3C-IN
Latching Plug-in DPDT --- --- --- MJN2CK
318 General Purpose Relay MJN
Specifications
Contact Data
Coil Data
Non-latching - AC
Non-latching - DC
Latching - AC
Note: 120% of nominal or greater (one second duration single pulse) unlatch voltage - - above this the relay latches again.
Maximum continuous voltage: 120% of nominal (one coil only).
Configuration SPDT, DPDT, 3PDT
Initial contact resistance 50 mΩ max.
Materials 3/16” diameter Ag-Alloy
Contact UL ratings 10 A 10 amp @ 28 VDC and 120/240 VAC at 80% pf, 1/3 hp @ 120 VAC, 1/2 hp @ 277/240/480/600 VAC
8.5 FLA - 36 LRA at 18 VDC, 3 amp @ 480/600 VAC at 80% pf, 10 amp @ 277 VAC resistive
20 A 20 amp @28 VDC and 120/240/277 VAC, 10 amp @ 480/600 VAC, 3.4 hp @ 120 VAC, 1-1/2 hp @
240 VAC, 17 FLA - 65 LRA at 300VAC
30 A 30 amp @ 28 VDC, 15 amp @ 480 / 600 VAC, 1hp @ 120 VAC, 1-1/2 hp @ 240 VAC
UL recognized file number E41643
Nominal
voltage
Resistance in Ohms ± 10% Nominal coil power Coil
voltages
Insulation
resistance
Pick up voltage at
25°C (77°F)
1 & 2 PDT 3PDT 1 & 2 PDT 3PDT
6 VAC 6.0 4.2 1.7 VA 2.0 VA 6 to 240 VAC
50/60 Hz
1,000 MΩ
min. @ 500
VDC
85% of nominal
12 VAC 21 18
24 VAC 75 72
120 VAC 2,250 1,700
240 VAC 9,100 7,200
Nominal
voltage
Resistance in Ohms ± 10% Nominal coil power Coil
voltages
Insulation
resistance
Pick up voltage at
25°C (77°F)
5 VDC 20 1.2 W 5 to 110 VDC 1,000 MΩ
min. @ 500
VDC
75% of nominal
6 VDC 32
12 VDC 120
24 VDC 470
48 VDC 1,800
110 VDC 10,000
Nominal
voltage
Latch coil
resistance in
Ohms ± 10%
Unlatch coil
resistance in
Ohms ± 10%
Nominal coil power Coil
voltages
Insulation
resistance
Operate voltage
(latch/unlatch) at 25°C (77°F)
(see note)
6 VAC 5.5 105 1.7 VA 2.0 VA 6 to 240 VAC
50/60 Hz
1,000 MΩ
min. @ 500
VDC
85% of nominal
12 VAC 22 445
24 VAC 88 1,740
120 VAC 2,090 17,430
General Purpose Relay MJN 319
Latching - DC
Note: 120% of nominal or greater (one second duration single pulse) unlatch voltage - - above this the relay latches again.
Maximum continuous voltage: 120% of nominal (one coil only).
Characteristics
Note: A latch pulse of 50 ms minimum at nominal voltage is recommended to insure positive latching.
Nominal
voltage
Latch coil
resistance in
Ohms ± 10%
Unlatch coil
resistance in
Ohms ± 10%
Nominal coil power Coil
voltages
Insulation
resistance
Operate voltage
(latch/unlatch) at 25°C (77°F)
(see note)
5 VDC 14 45 1.2 W 5 to 110 VDC 1,000 MΩ
min. @ 500
VDC
75% of nominal
6 VDC 20 64
12 VDC 80 275
24 VDC 330 1,070
48 VDC 1,290 2,850
110 VDC 5,125 10,750
Operate time 15 ms nominal; 20 ms maximum
Release time 6 ms nominal; 10 ms maximum
Latch time 13 ms nominal with a one second pulse of nominal voltage (See note)
Unlatch time 13 ms nominal with a one second pulse of nominal unlatch voltage after latching with
a one second pulse of nominal latching voltage (See note)
Operating
ambient
temperature
AC: 1 & 2 pole Operating -45° to 60°C (-49° to 140°F)
Storage -65° to 100°C (-85° to 212°F)
AC: 3 pole Operating -45° to 45°C (-49° to 113°F)
Storage -65° to 100°C (-85° to 212°F)
DC: 1, 2 & 3
pole
Operating -45° to 70°C (-49° to 158°F)
Storage -65° to 100°C (-85° to 212°F)
Insulation material High quality phenolic
Duty cycle Rated for continuous duty operation at 25% overvoltage
Shock 15 g’s 11±1 ms (non-operating test, no mechanical damage)
Vibration 0.1” DA or 10 g’s, 10 to 55 Hz (operating test, no contact chatter)
Life expectancy Electrical at
rated load
100,000 operations
Mechanical 10,000,000 operations
Dielectric strength Greater than 750 VAC, RMS 60 Hz across open contacts
Greater than 2,500 VAC, RMS 60 Hz all other mutually insulated elements
Terminals Quick Connect
Weight 64 g (2.3 oz) open relay
54 g (3.0 oz) enclosed relay

MJN1CF-AC240

Mfr. #:
Manufacturer:
Description:
General Purpose Relays GP Relay
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union