QP-200-3B

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
POWER GOOD / POWER FAIL(OPTIONAL)
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
800ms, 50ms at full load
24ms at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
PF>0.95/230VAC PF>0.98/115VAC at full load
75% 75%
CH1: 5.75 ~ 6.75V CH2:17.25 ~ 20.25V
72%
CH1:5.75 ~ 6.75V CH2:3.8 ~ 4.4V
3.5A/115VAC 2A/230VAC
COLD START 30A
<2mA / 240VAC
105 ~ 150% rated output power
CH1:5.75 ~ 6.75V CH2:13.8 ~ 16.2V
Protection type : Shut down o/p voltage, re-power on to recover
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
-10 ~ +60 (Refer to "Derating Curve")
10ms/1ms
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH non-condensing
±℃0.03%/ (0~50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
160.6K hrs min. MIL-HDBK-217F (25 )
215*115*50mm (L*W*H)
1.2Kg; 12pcs/15.4Kg/0.92CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. 33.3% Duty cycle maximum within every 30 seconds. Average output power should not exceed the rated power.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A, EAC TP TC 020
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
200W Quad Output with PFC Function
Universal AC input / Full range
Built-in active PFC function, PF>0.95
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan
CH1,2 can be adjustable from -5~+10%
With power good and fail signal output(Optional)
Built-in remote sense function for CH1,2
100% full load burn-in test
CH4 can set to positive after consult us before delivery(Optional)
Fixed switching frequency at PFC:67KHz PWM:134KHz
3 years warranty
Features :
QP-200 series
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 6)
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
QP-200D QP-200F QP-200-3A
5V 5V
CH2 CH2
24V
CH3 CH3 CH3
-12V
CH4 CH4 CH4
15V 24V -15V 3.3V 12V -5V
15A 15A 15A3A 0.7A 3A 3A 0.7A 15A 6A 0.7A
3 ~ 20A 3 ~ 20A 3 ~ 20A0 ~ 6A 0.4 ~ 5A 0 ~ 1A 0 ~ 5A 0.4 ~ 5A 0 ~ 1A 0 ~ 20A 0.5 ~ 8A 0 ~ 1A
203.4W 202.5W 200W
100mVp-p
20A
CH1: 4.75 ~ 5.5V CH2: 11.4 ~ 13.2V CH1: 4.75 ~ 5.5V CH2: 14.25 ~ 16.5V CH1: 4.75 ~ 5.5V CH2: 3.14 ~ 3.63V
150mVp-p 150mVp-p
6A
150mVp-p
1A
150mVp-p
6A
150mVp-p
6A
150mVp-p
1A
100mVp-p
20A
150mVp-p
8A
150mVp-p
1A
100mVp-p
20A
100mVp-p
20A
±3.0% ±3.0% ±3.0% ±3.0% ±3.0% ±3.0%+10,-6% ±6.0% +10,-6% ±6.0% +8,-10% ±6.0%
±1.0%±1.0%±1.0% ±2.0% ±1.0% ±1.0% ±2.0% ±1.0% ±1.0%±1.0% ±2.0% ±1.0%
±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0%
±6.0% ±2.0% ±6.0% ±6.0%
Shut down o/p voltage, recovers automatically after temperature goes down
File Name:QP-200-SPEC 2018-01-15
INPUT
OVER TEMPERATURE
PEAK CURRENT
Note.4
Protection type : Constant current limiting, recovers automatically after fault condition is removed
CH1 CH1 CH1
OUTPUT NUMBER
12V
CH2
4A
7A
5V
EMC IMMUNITY
EMC EMISSION
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
800ms, 50ms at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
72% 72% 74%
<2mA / 240VAC
105 ~ 150% rated output power
CH1:5.75 ~ 6.75V CH2:3.8 ~ 4.4V
Protection type : Shut down o/p voltage, re-power on to recover
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
-10 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH non-condensing
±℃0.03%/ (0~50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
160.6K hrs min. MIL-HDBK-217F (25 )
215*115*50mm (L*W*H)
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A, EAC TP TC 020
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
200W Quad Output with PFC Function
Features :
QP-200 series
ENVIRONMENT
SAFETY &
EMC
(Note 6)
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
QP-200-3B QP-200-3C QP-200-3D
5V 5V 5V3.3V 12V -12V 3.3V 15V -15V 3.3V -12V
15A 15A 10A15A 6A 0.7A 15A 5A 0.7A 0.7A
3 ~ 20A 3 ~ 20A 3 ~ 15A0 ~ 20A 0.5 ~ 8A 0 ~ 1A 0 ~ 20A 0.5 ~ 6A 0 ~ 1A 0 ~ 20A 0.4 ~ 5A 0 ~ 1A
204.9W 210W 203.9W
100mVp-p
CH1: 4.75 ~ 5.5V CH2: 3.14 ~ 3.63V CH1: 4.75 ~ 5.5V CH2: 3.14 ~ 3.63V CH1: 4.75 ~ 5.5V CH2: 3.14 ~ 3.63V
100mVp-p 150mVp-p 150mVp-p 100mVp-p 150mVp-p 150mVp-p 100mVp-p 150mVp-p 150mVp-p100mVp-p 100mVp-p
±3.0% ±3.0% ±3.0% ±3.0% ±3.0% ±3.0%+8,-10% ±6.0% +10,-6% ±6.0% +10,-6% ±6.0%
±1.0%±1.0%±1.0% ±2.0% ±1.0% ±1.0% ±2.0% ±1.0% ±1.0%±1.0% ±2.0% ±1.0%
±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0% ±2.0%±6.0% ±2.0% ±6.0% ±6.0%
Shut down o/p voltage, recovers automatically after temperature goes down
File Name:QP-200-SPEC 2018-01-15
INPUT
OVER TEMPERATURE
POWER GOOD / POWER FAIL(OPTIONAL)
10ms/1ms
FUNCTION
Protection type : Constant current limiting, recovers automatically after fault condition is removed
20A 20A 8A 1A 20A 7A 1A20A 20APEAK CURRENT
Note.4
Universal AC input / Full range
Built-in active PFC function, PF>0.95
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan
CH1,2 can be adjustable from -5~+10%
With power good and fail signal output(Optional)
Built-in remote sense function for CH1,2
100% full load burn-in test
CH4 can set to positive after consult us before delivery(Optional)
Fixed switching frequency at PFC:67KHz PWM:134KHz
3 years warranty
1.2Kg; 12pcs/15.4Kg/0.92CUFT
CH1 CH1 CH1
OUTPUT NUMBER CH2 CH2 CH2CH3 CH3 CH3CH4 CH4 CH4
24ms at full load
PF>0.95/230VAC PF>0.98/115VAC at full load
3.5A/115VAC 2A/230VAC
COLD START 30A
24V
15A 4A
20A 6A 1A
EMC IMMUNITY
EMC EMISSION
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. 33.3% Duty cycle maximum within every 30 seconds. Average output power should not exceed the rated power.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
AC CURRENT (Typ.)
800ms, 50ms at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
74%
<2mA / 240VAC
105 ~ 150% rated output power
CH1:5.75 ~ 6.75V CH2:3.8 ~ 4.4V
Protection type : Shut down o/p voltage, re-power on to recover
UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
-10 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH non-condensing
±℃0.03%/ (0~50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
160.6K hrs min. MIL-HDBK-217F (25 )
215*115*50mm (L*W*H)
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A, EAC TP TC 020
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
200W Quad Output with PFC Function
Features :
QP-200 series
ENVIRONMENT
SAFETY &
EMC
(Note 6)
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
QP-200-3E
3.3V
CH2
24V
CH3
-15V
CH4
10A 15A 4A 0.7A
3 ~ 15A 0 ~ 20A 0.4 ~ 5A 0 ~ 1A
206W
100mVp-p
20A 20A 6A 1A
CH1: 4.75 ~ 5.5V CH2: 3.14 ~ 3.63V
100mVp-p 150mVp-p 150mVp-p
±3.0% ±3.0% +10,-6% ±6.0%
±1.0%±1.0% ±2.0% ±1.0%
±2.0% ±2.0% ±6.0% ±2.0%
Shut down o/p voltage, recovers automatically after temperature goes down
INPUT
POWER GOOD / POWER FAIL(OPTIONAL)
10ms/1ms
FUNCTION
Protection type : Constant current limiting, recovers automatically after fault condition is removed
PEAK CURRENT
Note.4
File Name:QP-200-SPEC 2018-01-15
Universal AC input / Full range
Built-in active PFC function, PF>0.95
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan
CH1,2 can be adjustable from -5~+10%
With power good and fail signal output(Optional)
Built-in remote sense function for CH1,2
100% full load burn-in test
CH4 can set to positive after consult us before delivery(Optional)
Fixed switching frequency at PFC:67KHz PWM:134KHz
3 years warranty
1.2Kg; 12pcs/15.4Kg/0.92CUFT
CH1
OUTPUT NUMBER
24ms at full load
PF>0.95/230VAC PF>0.98/115VAC at full load
3.5A/115VAC 2A/230VAC
COLD START 30A
5V
EMC IMMUNITY
EMC EMISSION
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. 33.3% Duty cycle maximum within every 30 seconds. Average output power should not exceed the rated power.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os

QP-200-3B

Mfr. #:
Manufacturer:
Description:
Switching Power Supplies 204.9W 5/15 3.3V/15A 12V/6A -12V/0.7A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet