D1U3CS-W-1300F-12-Hx4EC Series
81mm Front End AC-DC Power Converter
D1U3CS-W-1300F-12-Hx4EC.A01 Page 4 of 5
www.murata-ps.com/support
Signal Pin Assignment Signal Name Description Current (Amps per Pin)
C3 PWR_GD Power Good signal. An active TTL HIGH signifi es when the output is within regulation limits. N/A
C4 FAN_FAIL Fan Fail signal (failure or locked rotor) N/A
D1 A0 I
2
C LSB (Least Signifi cant Bit) Address Line N/A
D2 A1 I
2
C MSB (Most Signifi cant Bit) Address Line N/A
D3 S_INT System Interrupt N/A
D4 N/A Reserved; no end user connection N/A
MATING CONNECTOR
Supplier Press Fit, Straight Press Fit, Right Angle Solder Straight
Solder Right Angle
FCI --- 51761-10002406AA ---
---
WIRING DIAGRAM FOR OUTPUT
CURRENT SHARING NOTES
1. Main 12VDC Output: Analogue active share bus. The ISHARE bus (Pin B3) must be connected on all sharing modules. It is not required that the SENSE signals are connected to the remote load for current share
to operate correctly.
2. Up to eight (8) power modules can be connected in parallel (non-redundant) or N+1 confi guration. The current share bus is analogue bi-directional (can source or sink current from the ISHARE bus). The voltage
of the bus would measure 8VDC for a single power module at 100% load; for two (2) modules sharing a common load the ISHARE bus voltage would be 4V for a perfect 50/50 current share scenario.
3. VSTANDBY output power modules can also be connected in parallel and have internal output isolation devices; however the combined available power is limited to that available from a single power module
(3.3V or 5V; 20W) irrespective of the number of modules connected in parallel.
+12V GND
+12VRS (Main Output Remote Sense)
+12VRS_RETURN
+12V OUT
B2
PB4-6
PB1-3
A2
Dotted lines show optional remote sense connections.
Optional remote sense lines can be attached to a load that is a distance
away from the power supply to improve regulation at the load.
D1U3CS
12V load
A1
A6,B6,C6,D6
A5,B5,C5,D5
FET, BJT, wire
or switch (debounced )
to turn on +12V main output
+VSB load
+VSB
PS_ON_L
+VSB GND
B4 PS_INHIBIT/PS_KILL
D1U3CS
B3
+12V_ISHARE
PS_INHIBIT/PS_KILL
B4
A6,B6,C6,D6+VSB GND
PS_ON_L A1
A5,B5,C5,D5+VSB
B3
A2
+12VRS_RETURN
+12V_ISHARE
+12V GND
+12V OUT
+12VRS (Main Output Remote Sense)
B2PB4-6
PB1-3