https://www.phoenixcontact.com/us/products/2800120
09/10/2014Page3/5
Lightning arrester type 1-FLT-PLUS CTRL-1.5/I-2800120
Technical data
Protective circuit
Voltage protection level U
p
≤ 1.5 kV
Voltage protection level U
p
(L-N)
≤ 1.5 kV
Voltage protection level U
p
(L-PEN)
≤ 1.5 kV
Response time ≤ 100 ns
Response time (L-N) ≤ 100 ns
Response time (L-PEN) ≤ 100 ns
Max. backup fuse with branch wiring 500 A (NH-gL)
Short-circuit resistance I
P
with max. backup fuse (effective)
50 kA
Follow current quenching capacity If 50 kA
Connection, protective circuit
Connection method Screw connection
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M6
Tightening torque 8 Nm
Stripping length 19 mm
Conductor cross section stranded min. 16 mm²
Conductor cross section stranded max. 35 mm²
Conductor cross section solid min. 10 mm²
Conductor cross section solid max. 50 mm²
Conductor cross section AWG/kcmil min. 6
Conductor cross section AWG/kcmil max 1
Standards and Regulations
Standards/regulations IEC 61643-1 2005
DIN EN 61643-11 2002
DIN EN 61643-11/A11 2007
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27140201
eCl@ss 5.0 27140201
eCl@ss 5.1 27140201
eCl@ss 6.0 27140201