Connection Note for axial connection method The specified conductor
cross-sections refer to the geometric cross-section of the used
conductor.The use of conductors with a geometric cross-
section that deviates greatly from the nominal cross-section
of the conductor should be checked first.The wiring space of
the axial screw technology has been designed for fine strand
conductors as per VDE 0295 class 5. Deviating conductor
superstructures (e.g. class 6 conductors) must be checked before
use.Connection It must be ensured before installation that the
ball screw is completely turned back (chamber is open). Twisting
the conductors is not allowed. The cores must be pushed up to
the end of the contact chamber (until the contact is insulated).
Keep the core in this position and tighten it using an Allen key.
The required core end must be cut before a reconnection.
Tightening the connection screw is allowed only once in order to
prevent a breakage of the litz wire.
Material data
Contact material Copper alloy
Contact surface material Ag
Contact carrier material PC
Certificates / Approvals
Certification CUL, GOST, UL
Accessories
Item Designation Description
Plug/Adapter
1636981 HC-M-MHR-PE16 Cable lug for HEAVYCON-MODULAR; PE connection extension
to 16 mm
2
, for crimping with crimp pliers