https://www.phoenixcontact.com/pi/products/2801041
04/30/2017Page2/4
Lightning/surge arrester type 1/2-VAL-MS-T1/T2
335/12.5/1+0-2801041
Technical data
Ambient conditions
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification I / II
T1 / T2
T1
EN type T1 / T2
T1
IEC power supply system TN-S
TN-C
TT
Mode of protection L-N
L-PEN
Mounting type DIN rail: 35 mm
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Design DIN rail module, two-section, divisible
Surge protection fault message optical
Protective circuit
Nominal voltage U
N
240V AC (TN-C, TN-S)
240V AC (TT)
Nominal frequency f
N
50 Hz (60 Hz)
Maximum continuous voltage U
C
335 V AC
Rated load current I
L
80 A
Residual current I
PE
≤ 800 µA
Standby power consumption P
C
≤ 270 mVA
Nominal discharge current I
n
(8/20) µs
12.5 kA
Maximum discharge current I
max
(8/20) µs
50 kA
Impulse discharge current (10/350)µs, charge 6.25 As
Impulse discharge current (10/350)µs, specific energy 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value l
imp
12.5 kA
Total discharge current I
total
(8/20)µs
12.5 kA
Total discharge current I
total
(10/350)µs
12.5 kA
Short-circuit current rating I
SCCR
25 kA