1
Solid-state Timer H3Y
Miniature Timer Compatible with the MY
Relay
Large
transparent time-setting knob facilitates time
setting. Flat-blade and Phillips screwdrivers can
also be used for time setting.
Approved by UL and CSA.
Pin
configuration compatible with
MY Power Relay
.
LED indication for power and output statuses.
Conforms to EMC standards.
High repeat accuracy.
RC
Ordering Information
Operation/resetting
t
Time-limit
contact
T
ime ranges
Supply voltage
Model
Ope a o / ese g
system
ecoac
e a ges
Supp y o age
Surface /DIN-track
mounting (with socket)
T
ime-limit operation/
lf tti
DPDT
0.1 s to 30 min
1
10 V
AC
H3Y-2
eoeao/
self-resetting
0so30
220 V
AC
3
24 VDC
4PDT
1
10 V
AC
H3Y-4
220 V
AC
3
24 VDC
Note:
Specify the model number
, supply voltage, and rated time when ordering.
Ex. H3Y-2 1
10 V
AC 1 s
Rated time
Supply voltage
Accessories
Track
mounted socket (see note )
Back connecting socket
ac ou ed soc e (see o e )
Solder terminal
W
ire-wrap terminal PC terminal
PYF08A, PYF08A-N, PYF08A-E
PY08 PY08QN(2) PY08-02
PYF14A, PYF14A-N, PYF14A-E
PY14 PY14QN(2) PY14-02
Note: T
rack mounted socket can be used as a front connecting socket.
Specifications
Time Ranges
Rated
time
1 s 5 s
10 s 30 s 60 s
3 min 30 min
T
ime setting
range
0.1 to 1 s 0.2 to 5 s
0.5 to 10 s 1.0 to 30 s 2.0 to 60 s
0.1 to 3 min 1.0 to 30 min
H3Y
H3Y
2
Ratings
Item H3Y-2/H3Y-4
Rated
supply voltage
1
10, 220 V
AC (50/60 Hz), 24 VDC (see note)
Operating voltage range
85% to 1
10% of rated supply voltage
Power consumption
100 V
AC: Relay ON:
1.5 V
A (1.3 W)
Relay OFF:
0.8 V
A (0.5 W)
200 V
AC: Relay ON:
1.8 V
A (1.5 W)
Relay OFF:
1.2 V
A (0.9 W)
24 VDC: Relay ON:
0.9 W
Relay OFF:
0.07 W
Control outputs H3Y
-2: 5 A at 250 V
AC, resistive load (cosφ
= 1)
H3Y
-4: 3 A at 250 V
AC, resistive load (cosφ
= 1)
Note:
With DC ratings, single-phase full-wave rectified power sources may be used.
Characteristics
Accuracy
of operating time
±
2% max.
Setting error ±
10% (max. time division at rated voltage and room temperature)
Reset time
0.1 s max.
Influence of voltage
±
2% max.
Influence of temperature
±
5% max.
Insulation resistance
100 M
min. (at 500 VDC)
Dielectric strength
2,000 V
AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed
non-current-carrying metal parts) (see note)
2,000 V
AC, 50/60 Hz for 1 min (between operating power circuit and control output) (see note)
2,000 V
AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) (see note)
1,500 V
AC, 50/60 Hz for 1 min (between dif
ferent pole contacts; 4-pole model)
1,000 V
AC, 50/60 Hz for 1 min (between non-continuous contacts)
V
ibration resistance
Destruction:
10 to 55 Hz with 1.0-mm double amplitude
Malfunction:
10 to 55 Hz with 1.0-mm double amplitude
Shock resistance
Destruction:
1,000 m/s
2
(approx. 100G)
Malfunction:
100 m/s
2
(approx. 10G)
Ambient temperature
Operating: –10
°
C to 50
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical:
10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical:
H3Y
-2: 500,000 operations min. (5 A at 250 V
AC, resistive load at 1800 operations/h)
H3Y
-4: 200,000 operations min. (3 A at 250 V
AC, resistive load at 1800 operations/h)
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
IEC801-2:
4 kV contact discharge (level 2)
4 kV air discharge (level 2)
Immunity RF-interference:
ENV50140:
10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance:
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
IEC801-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards
UL (File No. E41515), CSA (File No. LR22310)
Conforms to EN50081-2, EN50082-2
Weight
Approx. 50 g
Note: T
erminal screw sections are excluded.
H3Y
H3Y
3
Engineering Data
H3Y-2
Switching operations (x 10 )
3
Load current (A)
H3Y-2
H3Y-4
Switching operations (x 10 )
3
Load current (A)
Switching operations (x 10 )
3
Load current (A)
H3Y-4
Switching operations (x 10 )
3
Load current (A)
250 VAC, cosφ
= 1
24 VDC, cosφ
= 1
250 VAC, cosφ
= 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ
= 1
24 VDC, cosφ
= 1
250 VAC, cosφ
= 0.4
24 VDC, L/R = 7 ms
Reference: A
maximum current of 0.6 A can be
switched at 125 VDC (cosφ
= 1).
Maximum current of 0.2 A can be
switched if L/R is 7 ms. In both
cases, a life of 100,000 operations
can be expected.
The minimum applicable load is
1 mA at 5 VDC (P reference value).
Reference:
A maximum current of 0.5 A can be
switched at 125 VDC (cosφ
= 1).
Maximum current of 0.2 A can be
switched if L/R is 7 ms. In both
cases, a life of 100,000 operations
can be expected.
The minimum applicable load is
1 mA at 1 VDC (P reference value).
Operation
Timing Chart
H3Y-2 H3Y-4
Time limit contact
NC (9-1, 12-4)
Time limit contact NC
(9-1, 10-2, 1
1-3, 12-4)

PYF14A

Mfr. #:
Manufacturer:
Omron Automation and Safety
Description:
Relay Sockets & Hardware SOCKET FOR MY
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS